BLOWER SPEED ADJUSTMENT

FORM 145.15-IOM7 (412)

BLOWER SPEED ADJUSTMENT

The RPM of the supply air and condenser air blowers will depend on the required CFM, and the static resistances of both the supply/discharge and the return/intake duct systems. With this information, the RPM for the blowers can be determined from the blower performance tables. Adjustment of blower speed is accomplished as follows:

1)Loosen belt tension by moving motor towards the blower shaft via the adjustable mounting.

2)Loosen the setscrew in the adjustable motor pulley flange. Remove external key on pulleys 4 in. diameter and larger.

3)Blower speed will increase when moveable flange is adjusted towards the fixed flange (closed). Blower speed will decrease when the moveable flange is adjusted away from the fixed flange (opened). Pulleys are adjustable only in half-turn increments. Do not open pulley more than five full turns for "4L" and "A" belts, or six full turns for "B" belts.

4)Once the pulley has been opened/closed the appropriate number of turns, replace the external key and tighten the adjustment setscrew. Proper torque is 110-130 in.-lbs.

5)Install drive belt and adjust motor mount to tension belt.

BELT TENSION ADJUSTMENT

LD13547

DEFLECTION FORCE VERSUS DRIVE BELT CROSS-SECTION

20