I n s t a l l a t i o n

SINGLE FLOOR PLAN

MULTIPLE FLOOR PLAN

 

 

 

 

 

 

IMAGE 1A

 

 

IMAGE 1B

 

 

 

 

 

 

 

Install smoke alarms on sloped, peaked or cathedral ceilings at or within 0.9 m (3') of the highest point (measured horizontally). NFPA Standard 72 states: “Smoke alarms in rooms with ceiling slopes greater than 0.3 m in 2.4 m (1 foot in 8 feet) horizontally shall be located on the high side of the room.” NFPA Standard 72 states: “A row of detectors shall be spaced and located within 0.9 m (3') of the peak of the ceiling measured horizontally” (Image 2B).

IMAGE 1C TOTAL HOME PROTECTION

I n s t a l l a t i o n

Locations to Avoid

Do not install within 0.9 m (3') of the following: The door to a kitchen, or a bathroom that contains a tub or shower, forced air ducts used for heating or cooling, ceiling or whole house ventilating fans, or other high air-flow areas.

Do not place the alarm where drapes or other objects will block the sensor. Smoke must be able to reach the sensor to accurately detect conditions.

Do not install in peaks of vaulted ceilings, “A” frame ceilings or gabled roofs. (Less than 10 cm (4") from the peak of an “A” frame type ceiling.)

Install at least 30.5 cm (12") away from fluorescent lights as electronic noise may cause nuisance alarms.

Keep out of insect infested areas. Avoid excessively dusty, dirty or greasy areas. Dust particles may cause nuisance alarms or failure to alarm.

Extreme temperatures may effect the sensitivity of the alarm. Do not install in areas where the temperature is colder than 4.4°C (40°F) or hotter than 37.8°C (100°F).

Do not install in areas where the relative humidity (RH) is greater than 85%. Very humid areas, with moisture or steam, can cause nuisance alarms.

Avoid placing ionization smoke alarms in kitchen areas. Normal cooking may cause nuisance alarms. If a kitchen alarm is desired, it should have an alarm silence feature or be a photoelectric type.

Do not place in the garage. Particles of combustion are present when you start your automobile.

Smoke alarms are not to be used with detector guard s unless the combination (alarm and guard) has been evaluated and found suitable for that purpose.