• Install smoke alarms on sloped, peaked or cathedralceilings at or within 0.9 m (3') of the highest point(measured horizontally). NFPA Standard 72 states: “Smokealarms in rooms with ceiling slopes greater than 0.3 m in2.4 m (1' in 8') horizontally shall be located on the highside of the room.” NFPA Standard 72 states: “A row ofdetectors shall be spaced and located within 0.9 m (3') ofthe peak of the ceiling measured horizontally” (Image 2Band Image 2C).