Installation Instructions
Beacon | + From Controller | To Next Unit |
- |
|
Sounder | + | 1st Stage |
- | ||
|
| 2nd Stage |
|
| 3rd Stage |
1st Unit | 2nd Unit |
EN | Installation Manual |
Installation
a. The sounder is installed by first mounting the base unit and making the external wring connectionsto the base. The head unit then automatically connectswhen it is attachedto the base.
b. The sounder head is separated from the base by unlocking the four
(Recommended screwdriver: Philips No. 2, min 100mm long).
c. Note that the head only fits onto the base one way around. If a beacon is fitted, care should be taken when mounting the base to ensure that the beacon will be positioned in the desired orientation after the sounder is attached
Wiring
The sounder and beacon have separate wiring terminals. Each terminal is duplicated to enable simple
| Line | Terminal Marking | ||||||
| Sounder Positive Supply (10 to 60V DC) |
|
|
|
|
| + |
|
|
|
|
|
|
|
| ||
| Sounder Negative Supply (0V) |
|
|
|
|
| - |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
| 2nd Stage Alarm Control (Connect to 0V to activate) |
|
|
|
|
| S2 |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
| 3rd Stage Alarm Control (Connect to 0V to activate) |
|
|
|
|
| S3 |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
| Beacon Positive Supply (10 to 60V DC) |
|
|
|
|
| + |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
| Beacon Negative Supply (0V) |
|
|
|
|
| - |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
Controls
a.Tone Selection
The first and second stage alarm tones are independently set using
b.Volume Control
The sound output of the unit can be reduced by up to 20dBA by adjusting the potentiometer.
c.Beacon Flash Controls (If fitted)
The flash mode of the beacon can be altered using the
|
| XENON BEACON |
| LED BEACON | |||||
| Switch | Off |
| On |
| Off |
| On |
|
|
|
|
|
| |||||
| 1 | 60 flashesper min |
| 30 flashes per min |
| Single Flash |
| Double Flash |
|
| 2 | Single Flash |
| Double Flash |
| Flashing |
| Static |
|
Technical Specification:
Supply Voltage Range | |
Current – Sounder | |
Current | Xenon - 250mA Average, 700mA Peak*, |
(Where fitted) | LED - 18mA (Flashing) or 65mA (Static)* |
Peak Sound Level | |
| (Typ.105dBA@ 24V,Tone1) |
Number of Tones | 64 |
Volume Control | 20dBA typical |
Remote Tone Switching | Provision for 3 alarm stages |
| (Negative voltage activation) |
Operating Temperature | |
Casing | High Impact Polycarbonate/ABS |
IP Rating | IP66 |
Synchronisation | Automatic with Klaxon Nexus and |
| Sonos Sounders |
*depends on selected tone and input voltage. See tone table for details.
The European directive “Waste Electrical and Electronic Equipment” (WEEE) aims to minimise the impact of electrical and electronic equipment waste on the environment and human health. To conform with this directive, electrical equipment marked with this symbol must not be disposed of in European public disposal systems. European users of electrical equipment must now return