Klaxon 17-970303 manual Installation, Surface Mounting, Terminations/Connections, Flush Mounting

Models: 17-970303

1 3
Download 3 pages 34.38 Kb
Page 1
Image 1
Klaxalarm Boxer (17-970303)

Klaxalarm Boxer (17-970303)

Battery Operated - Manual Call Point/Sounder

The Manual Call Point has a built-in alarm sounder and is powered by batteries. Up to 12 units can be connected together using 2 core screened fire proof cable (the screen core is used as a negative). The indicating LED will light on operation of the device(s) and switch off on resetting.

The Batteries should be replaced once every 12 months. The unit does not draw any current from the batteries until operated. There is no low battery warning feature but as the battery voltage falls a slight drop in sound output is noticeable during normal testing.

1. Installation

Surface Mounting

Fix the surface back box to a flat vertical surface using at least two of the four mounting holes provided.

The back box may be drilled to allow cable access, a step drill is the most efficient and least stressful to the moulding. A 20mm hole is provided in the rear.

NOTE Please ensure that the spade connectors are located exactly as per diagram (shown right) else the battery may foul against them

Terminations/Connections

When interlinking more than one unit - cabling may be connected into the terminals provided (Red=Permanent positive, Blue=Common Negative, Yellow=Switched Positive). Although there are three conductors a 2 core screen cable can be used, as the screen may be utilised.

If using Pirelli FP200 then wire as Red:RED, Black:YELLOW, Screen:BLUE.

Flush Mounting

The Call Point may be flush mounted utilising the optional flush bezel, combined with any standard single gang flush mounting back box (with a minimum internal depth of 25mm). After installing the back box securely, attach the bezel using the two M3 screws

Call Point 1st fix testing

Please remember that all high voltage testing must be carried out before the installation of the Call Point front unit as this may cause damage.

Page 1
Image 1
Klaxon 17-970303 manual Installation, Surface Mounting, Terminations/Connections, Flush Mounting, Klaxalarm Boxer