13.0 CHECKING THE GAS CONNECTIONS

WARNING

Never use an open flame to check for leaks.

Turn on gas supply and test for gas leaks using a gas leak test solution (also referred to as bubble leak solution).

NOTE: using a soapy water solution (50% dish soap, 50% water) is an effective leak test solution, but it is not recommended, because the soap residue that is left on the pipes/fittings can result in corrosion over time.

A. Light the appliance (refer to the lighting instructions label in the con­ trol compartment or on Page 14).

B. Brush all joints and connections with the gas leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob (off/pilot/on) to the “OFF” position. Either tighten or refasten the leaking connection, then retest as described above.

C. When the gas lines are tested and leak free, be sure to rinse off the leak testing solution.

D. Observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.

14.0 GAS PRESSURE CHECK

The heater regulator controls the burner pressure which should be checked at the pressure test points located on the control valve itself (shown in Figure 7) for burner (manifold) and regulator (inlet) setting pressures.

The pressure should be checked with the gas heater burning and the control set to high flame.

The pressure test points are located on the gas valve. To access the valve and the test points, firstly remove the control knob spindle from the valve spindle by removing the retaining clip shown in Figure 5.

Retaining clip

Figure 5 - Remove Retaining Clip

Withdraw the control knob and spindle from the heater, remove the gas valve cover plate by removing the four retaining screws indicated in Figure 6.

Figure 6 - Remove Gas Valve Cover

The pressure test points are located as shown in Figure 7. An alternative burner (manifold test point is located below the left hand side of the burner as shown in Figure 8.

The pressure regulator on manual models is preset and locked to avoid tampering. If the pressure is not as specified in Table 1 on Page 3, replace the regulator with P/N H6063.

Replace the test point screws after pressure measurement ensuring no gas leaks. All instructions must be handed to the user for safekeeping.

Regulator (Inlet)

Burner (Manifold) Pressure

Figure 7 - Manifold and Inlet Pressure Taps

Figure 8 - Alternate Test Point