Table 2 shows the main burner gas orifice size for the elevations indicated.
Model | Orifice Size | Elevation | |
No. | Nat. | Prop. | Feet |
| (meters) | ||
| Gas | Gas | |
|
| ||
|
|
|
|
EBVI25 | #41 | #53 | |
| (.096") | (.0595") | |
|
|
|
|
EBVI30 | #37 | 1/16" | |
| (.104") | (.0625") | |
|
|
|
|
Table 2 |
|
|
|
|
|
|
|
Tables 3 and 4 show the gas pressure requirements for all models:
Inlet Gas Supply Pressure (all models)
Fuel # | Minimum | Maximum |
|
|
|
Natural Gas | 4.5" WC | 10.5" WC |
| (1.12 kPa) | (2.61 kPa) |
Propane | 11.0" WC | 13.0" WC |
| (2.73 kPa) | (3.23 kPa) |
Table 3
Manifold Gas Supply Pressure (all models)
Fuel # | Low | High |
|
|
|
Natural | (Lo) 1.6" WC | (Hi) 3.5" WC |
Gas | (.40 kPa) | (.87 kPa) |
|
|
|
Propane | (Lo) 6.3" WC | (Hi) 10.0" WC |
| (1.57 kPa) | (2.49 kPa) |
Table 4
Test gauge connections are provided on the front of the millivolt gas control valve (identi- fied IN for the inlet and OUT for the manifold side). See Figures 1 & 2.
This appliance must be isolated from the gas supply piping system (by closing its individual manual
This appliance and its individual
This appliance must not be connected to a chimney or flue serving a separate
WARNING
Carbon monoxide poisoning: Early signs of carbon monoxide poisoning are similar to the flu withheadaches,dizzinessand/or nausea. If you have these signs, obtainfreshairimmediately.Turn offthegassupplytotheappliance and have it serviced by a quali- fied professional, as it may not be operating correctly.
WARNING
Failure to comply with the installation and operating instructions provided in this document will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appliance and/or its operating controls is dangerous. Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
During the first few burns of these appliances there will be some odor due to the curing of the high temperature paint and burning off of lubricants used in the manufacturing process.
Depending on your use, the
blower during
IMPORTANT
Keep your house well ventilated during the curing process. The odor and haze emitted by the curing process can be quite noticeable and may set off a smoke detector.
LIGHTING MILLIVOLT APPLIANCES
To light millivolt appliances refer to the detailed lighting instructions found on Page 15 (Eng- lish) and Page 16 (French). Millivolt appliance lighting instructions may also be found on the
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
GAS CONTROLS
These millivolt appliances are fitted with a burner Off/On Switch, located on the side surround panel as shown in Figure 4 on Page 4. Once the pilot is lit, and valve knob is in the ON position, the Off/On switch will control the appliance Off/On operation. To operate, toggle the switch between its ON and OFF positions.
Variable Flame Height Adjustment
These millivolt appliances are equipped with variable gas control valves. Flame height may be adjusted through a range between fixed low and high settings by rotating the HI/LO knob on the valve (see Figures 1 & 2) while the appliance is in operation.
Model EBVI30
Honeywell Millivolt Gas Valve Controls
|
|
| PIEZO | CONVERTIBLE |
PILOT |
|
| IGNITER | |
ADJUSTMENT | GAS CONTROL | HI/LO REGULATOR | ||
SCREW | KNOB |
|
| (adjusts flame height |
|
|
|
| and heat output) |
TP/TH |
|
|
|
|
|
|
| O |
|
|
|
| NI |
|
|
|
|
| L |
|
|
| P | O |
TP | OL | I | H | |
|
| |||
|
|
| ||
FFO T |
|
|
| |
TH |
|
|
|
|
WIRING | INLET | OUTLET | ||
TERM- | PRESSURE | PRESSURE | ||
INALS | TAP | TAP |
Figure 1
MODEL EBVI25
SIT Millivolt Gas Valve Controls
GAS CONTROL
KNOB
|
|
| OT |
|
|
| IL |
F |
|
| P |
|
|
| |
T | O N |
|
|
it |
| TH | |
O | WO L | ||
L |
|
| |
I |
|
|
|
P | FO |
|
|
|
| TP | |
|
| H I | |
|
|
| |
|
|
| TPTH |
IN | OUT |
|
|
| OUTLET |
| CONVERTIBLE |
INLET |
| HI/LO REGULATOR | |
PRESSURE |
| ||
PRESSURE | TAP |
| (adjusts flame height |
TAP |
|
| and heat output) |
PIEZO |
|
|
|
IGNITER
Figure 2
3