INSTALLATION
This appliance is designed to be vented with a 4” x 6 5/8”
VERTICAL TERMINATION | VERTICAL TERMINATION |
|
| HORIZONTAL TERMINATION | |||||||||
WITH NO OFFSETS | WITH 2 OFFSETS |
|
| WITH 1 OFFSET | |||||||||
Min. Vertical Pipe Length: 5 feet | Min. Vertical Pipe From Appliance | to first | Min. Vertical Pipe From Appliance to offset: | ||||||||||
Max. Vertical Pipe Length: 25 | offset: 2 feet (*see note). |
|
| 2 feet (*see note). | |||||||||
feet | Min. Total Vertical Pipe Length: 5 feet |
|
| Max. Vertical Pipe Length: 25 feet | |||||||||
|
|
| Max. Total Vertical Pipe Length: 25 feet |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| 16 Feet Max. | ||
|
|
| For every 1 feet of |
|
|
|
|
|
|
|
|
| |
|
|
| vertical pipe (from |
|
|
|
|
|
|
|
|
| |
|
|
| unit to first offset), 2 |
|
|
|
|
|
|
|
|
| |
|
|
| feet of horizontal |
|
|
|
|
|
|
|
|
| |
|
|
| run is allowed (not |
|
|
|
|
|
|
|
|
| |
|
|
| to exceed 16 ft. |
|
|
|
|
| For every 1 feet of vertical | ||||
|
|
|
|
|
|
|
|
|
| pipe (from unit to first offset), | |||
|
|
| Example – with a 6’ ver- |
|
|
|
|
| 2 feet of horizontal run is | ||||
|
|
|
|
|
|
|
| allowed (not to exceed 16 ft. | |||||
|
|
| tical pipe off unit, 12’ of |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| horizontal run is allowed. |
|
|
|
|
| Example – with a 8’ ver- | ||||
|
|
|
|
|
|
|
|
|
| tical pipe off unit, 16’ of | |||
|
|
|
|
|
|
|
|
|
| horizontal run is allowed. | |||
| 5 Feet |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 25 |
|
|
|
|
| ||
|
|
|
| At 2’ Min. Vertical, 2’ Max. |
| ||||||||
| Min. |
|
| 5 Feet |
|
| Feet |
|
| ||||
| 25 Feet |
|
|
| Min. |
|
| Max. |
| Horizontal is allowed. |
| ||
|
|
|
|
| |||||||||
| Max. |
| Horizontal |
| 25 |
|
|
|
|
| Horizontal runs | ||
|
|
| runs require |
| Feet |
|
|
|
|
| |||
|
|
| ¼” rise per |
| Max. |
|
|
|
|
| require ¼” rise | ||
|
|
|
|
|
|
|
|
| per foot. | ||||
|
|
|
|
|
|
|
| ||||||
|
|
| foot. |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| * 2 Feet Min. | |||
|
|
| * 2 Feet Min. |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| Wall | ||
|
|
|
|
|
|
|
|
|
|
| Penetration | ||
|
|
|
|
|
|
|
|
|
|
| Detail | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Maximum total offsets allowed: Not to exceed 180 degrees.
Maximum allowable horizontal pipe run is 16 feet.
With 2 feet of vertical pipe installed from the appliance (* see note), a 2 foot maximum horizontal run allowed. For installations with more than 2 feet of vertical pipe, calculate allowable horizontal run as indicated in applicable illustration above.
See page 10 for Vent Termination Requirements.
Also see pipe manufacturers instructions for additional vent installation requirements. Horizontal vent clearances: 3“ minimum top 1“ minimum on bottom and sidewalls. Vertical vent clearances: 1” minimum.
Install vent support brackets every 4 feet of vertical pipe unless otherwise specified by vent manufacturer.
*Note: If using Propane Gas (LP), it may be necessary to install (as a minimum) 3 feet of vertical pipe from the appliance prior to an offset to ensure optimum product performance. This may be necessary due to variations in vent configuration and other numerous factors which affect exhaust flow and air delivery such as BTU value, ambient temperature, wind conditions, altitude, etc.
PAGE 7