3.Note the floor construction, i.e. 2 x 6’s, 2 x 8’s or 2 x 10’s, single or double joists, type and thickness of floor boards.
4.Use this information and consult your local building code to determine if you need addi- tional support.
If you plan to raise the fireplace and hearth extension, build the platform assembly then position fireplace and hearth extension on top. Secure the platform to the floor to prevent possible shifting.
WATERPROOFING THE FIREPLACE
Although the
To prevent this, the builder must provide a means to drain water from under the fire- place by building or installing a water collec- tor of the builder's choice, or installing a PVC
Note: The
Step 1. Seal all joints, gaps and corners around the bottom of the fireplace before positioning the fireplace on its location (Figure 4 ).
Step 2. Locate the drainage plug and remove it by depressing the locking tabs and pushing down through the outside air opening at the bottom of the fireplace.
Step 3. On the exposed hole, install a PVC threaded coupling reducer, 3/4" x 1/2" going from inside of the fireplace out. Apply a
Step 4. Holding the reducer coupling with a wrench, thread a 3/4", 90 degree, PVC elbow to the reducer until it is tight to the metal.
Note: Clearance at the nailing flange for both fireplace models is 0" (0mm).
Note: Adjacent wall considerations are for an adjacent wall on only a single side. Walls should not be placed at minimum distance at both sides of the fireplace.
INSTALLING THE FIREPLACE
Step 1. Slide the fireplace into prepared fram- ing or position fireplace in its final position and frame later.
The fireplace may not be recessed into a com- bustible floor. Maintain the floor to hearth clearance established by the fireplace lower front face.
Step 2. Insert the provided metal safety strips, beneath the fireplace as illustrated (Figures 5, 6 and 7 ). The safety strips should overlap ¹⁄₂" min. for continual coverage of the floor.
drain as follows:
Seal All |
|
Seams, | Access |
Joints | |
And | Drain Plug |
Corners | Through |
Around The | Air Inlet |
Bottom Of | Opening |
Fireplace |
|
Note: To assure proper drainage, the fireplace must be installed on a leveled surface.
Air Inlet
The installation of the air inlet is required for safe fireplace operation.
Step 1. Determine the location for air inlet, which can be installed through an outside wall. A 6 1/2" diameter hole will be required for installation of the air inlet assembly (see Figure 17 ).
Combustible Wall
Maintain
¹⁄₂" (13mm) Air Space at Sides and Back
¹⁄₂" (13mm)
Metal Safety Strip
Hearth Extension
Floor
Fireplace On
Drain Connector |
| |
(see Detail A ) |
| |
Threaded | Threaded | |
Reducer | ||
Elbow ³⁄₄” | ||
³⁄₄” x ¹⁄₂” | ||
@ 90° | ||
(PVC) | ||
(PVC) | ||
|
Detail A
CAUTION: AVOID INSTALLING THE AIR IN- LET WHERE THE OPENING COULD BE BLOCKED BY SNOW, BUSHES OR OTHER OBSTACLES. THE MAXIMUM HEIGHT FOR THE OUTSIDE AIR IS 50 FEET ABOVE THE HEARTH, PROVIDING THE AIR INLET IS TER- MINATED A MINIMUM OF THREE (3) FEET BELOW THE CHIMNEY CAP LEVEL.
Note: Air inlet ducts must not terminate in attic space.
CLEARANCES
Minimum clearance to combustibles for the fireplace is as follows; sides and back – ¹⁄₂" (13mm), combustible floor – 0" (0mm), adja- cent wall 18" (457mm), adjacent shielded wall
Figure 5
Combustible
Wall
Maintain
¹⁄₂" (13mm) Air Space at Sides and Back
¹⁄₂" (13mm)
Hearth Extension
Figure 4
(K factor of .84 or less 40" W x 40" H ) 12" (305mm), ceiling – 37 ¹⁄₂" (953mm). Refer to page 17 for more detail.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Metal Safety Strip | Platform | Floor |
Fireplace On Combustible Floor
Figure 6
5