20 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
IMPORTANT NOTES: 1.  All Ravelle™ 30 fireplace vertically terminated may only use 6-5/8” 
x 4” Secure Vent™ direct-vent pipe by Security Chimneys™ or GS 
direct-vent pipe by Dura-Vent®.
2.  If  the vent passes through a ceiling  or floor, a firestop - Security 
Chimneys part number SV4BF or Dura-Vent part number 963 – is 
required.
3.  If the vent passes through the roof, a roof flashing and storm collar 
are required.
4.  Allowable clearances from the vent pipe to combustible materials 
must be maintained. See Page 10 for these clearances.
5.  A  maximum  of either  two  45-degree elbows  or  two 90-degree 
elbows may be used. See Page 22 for allowable offsets.
6.  The  maximum system height is 30 feet (9.1M) and the minimum 
is 10 feet (3M).
Vertical Vent Termination ClearancesThe vent / air  intake termination clearances  above the high  side of an 
angled roof is as shown in the Figure 18.
Termination Heights For Vents 
Above Flat Or Sloped Roofs
Ref. NFPA 54 / ANSI Z223.1, 7.6
Roof Pitch * Feet * Meters
Flat to 6/12 1.0 0.3
6/12 to 7/12 1.25 0.38
7/12 to 8/12 1.5 0.46
8/12 to 9/12 2.0 0.61
9/12 to 10/12 2.5 0.76
10/12 to 11/12 3.25 0.99
11/12 to 12/12 4.0 1.22
12/12 to 14/12 5.0 1.52
14/12 to 16/12 6.0 1.83
16/12 to 18/12 7.0 2.13
18/12 to 20/12 7.5 2.29
20/12 to 21/12 8.0 2.44
12 
X 
Roof Pitch is X/12 
2 FT 
MIN. 
2 FT MIN. 
Lowest 
Discharge 
Opening 
H* 
*H = MINIMUM HEIGHT FROM ROOF TO 
LOWEST DISCHARGE OPENING OF VENT 
TERMINATION HEIGHTS FOR VENTS ABOVE 
FLAT OR SLOPED ROOFS 
Horizontal Overhang 
Vertical 
Wall 
Vent 
Termination 
Storm Collar 
Concentric 
Vent Pipe 
Flashing 
1 inch (25.4 mm) Minimum 
Clearance to Combustibles