8NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Installation of these appliances are approved for installation in New York
City in the US state of New York (MEA#: 138-07-E).
NEW YORK CITY, NEW YORK (MEA)COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS(Massachusetts Approval #G3-0806-6)
These appliances are approved for installation in the US state of Mas-
sachusetts if the following additional requirements are met:
• Install this appliance in accordance with Massachusetts Rules and
Regulations 248 C.M.R. Sec. 5.08 2(a) through 2(e).
• Installation and repair must be done by a plumber or gas fitter
licensed in the Commonwealth of Massachusetts.
• The flexible gas line connector used shall not exceed 36 inches (92
centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed
less than seven (7) feet above the finished grade must comply with the
following additional requirements:
• A hard wired carbon monoxide detector with an alarm and battery
back-up must be installed on the floor level where the gas fireplace
is installed. The carbon monoxide detector must comply with NFPA
720, be ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identification plate must be permanently mounted
to the exterior of the building at a minimum height of eight (8) feet
above grade and be directly in line with the horizontal termination.
The sign must read, in print size no less than one-half (1/2) inch in
size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUC-
TIONS.
• Must conform with all local, state and national installation codes.
In the absence of local codes, the installation must conform with
National Fuel Gas Code ANSI Z223.1 - latest edition, also known
as NFPA 54 (In Canada, the current CAN/CSA B149.1 installation
code). Refer to the National Fuel Gas Code and local zoning and
code authorities for details on installation requirements.
• Mobile home installations must conform with the Mobile Home
Construction and Safety Standard, Title 24 CFR, Part 3280 (in Canada
CAN/CSA Z240 MH), or, when such a standard is not applicable,
the Standard for Mobile Home Installations, ANSI A225.1 - latest
edition.
• Must be vented directly to the outside in accordance with the latest
edition of the National Fuel Gas Code and must never be attached
to a chimney serving a separate solid fuel burning appliance.
• Has been certified for use with either natural gas or propane.
• Is not for use with solid fuels.
• Is approved for sitting rooms and/or bedrooms.
For altitudes above 2,000 feet (In Canada 4,500 FT/1370 M), the orifice
should be de-rated by 4% for every 1,000 feet to maintain the proper
ratio of gas to air. Improper orifice sizing my result in damage and
unsafe conditions. Changing the orifice should only be done by a quali-
fied service technician. Contact your Lennox Hearth Products dealer for
proper orifice sizes.
Since there are always several potential sources of fire in any home, we
recommend installing smoke detectors. If possible, install the smoke
detector in a hallway adjacent to the room (to reduce the possibility of
occasional false activation from the heat produced by the appliance). If
your local code requires a smoke detector be installed within the same
room, you must follow the requirements of your local code. Check with
your local building department for requirements in your area.
This fireplace has been tested and certified by OMNI -Test Laboratories
to ANSI Z21.88 / CSA 2.33 Standard for Vented Gas Fireplace Heater
and CGA 2.17-M91 and UL 307B Gas Burning Heating Appliances for
Manufactured (Mobile) Homes in both USA and Canada.
This appliance has met all necessary ANSI Standards and is fully certified
for installation in any community. If there are any questions or if you
need further substantiation contact your Lennox Hearth Products dealer.
If you have further questions, please contact Lennox Hearth Products.
Check all local building and safety codes before installation. The installation
instructions and appropriate code requirements must be followed exactly
and without compromise. In the absence of local codes the following
standards and codes must be followed.
The Installation must conform to local codes or, in the absence of local
codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest
edition (In Canada, the current CAN/CSA-B149.1 installation code).
The appliance, when installed, must be electrically grounded and wired
in accordance with local codes or, in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70 - latest edition, or the Canadian
Electrical Code, CSA C22.1 - latest edition.
ORIFICE SIZE/ALTITUDE ADJUSTMENTSMOKE DETECTORSCODES AND APPROVALSTHE RAVELLE™ 30 FIREPLACECertificationGas appliances must be tested and certified by a nationally recognized
testing and certification laboratory to ANSI (American National Standard
Institute) gas appliance safety standards.