Compressor Delay (P5)
The defrost control has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode.
SUnits with defrost control 100269−02: The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is removed.
SUnits with defrost control 100269−04: The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is installed.
NOTE
when jumpering the TEST pins. Time Delay
The
Test Mode (P1)
A TEST option is provided for troubleshooting. The TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at
Defrost Control Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.
Table 6. Defrost Control (CMC1) Diagnostic LEDs
Mode | Green LED (DS2) | Red LED (DS1) | |
|
|
| |
No power to con- | OFF | OFF | |
trol | |||
|
| ||
|
|
| |
Normal operation / | Simultaneous Slow FLASH | ||
power to control | |||
|
| ||
|
|
| |
Alternating Slow FLASH | |||
lockout | |||
|
| ||
|
|
| |
High pressure | Slow FLASH | OFF | |
switch fault |
|
| |
|
|
| |
High pressure | ON | OFF | |
switch lockout |
|
| |
|
|
|