![New Outdoor Unit Placement](/images/new-backgrounds/35472/3547213x1.webp)
New Outdoor Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lift- ing heavy objects.
higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, detail B.
NOTE If necessary for stability, anchor unit to slab as described in figure 5, detail D.
Remove existing outdoor unit prior to placement of new | ELEVATING THE UNIT |
| ||||
outdoor unit. See Unit Dimensions on page 2 for sizing |
| |||||
Units are outfitted with elongated support feet as illustrated | ||||||
mounting slab, platforms or supports. Refer to figure 4 for | ||||||
in figure 5, detail C. |
| |||||
mandatory installation clearance requirements. |
| |||||
|
| |||||
POSITIONING CONSIDERATIONS | If additional elevation is necessary, raise the unit by | |||||
extending the height of the unit support feet. This may be | ||||||
Consider the following when positioning the unit: | ||||||
achieved by using a 2 inch (50.8mm) schedule 40 female | ||||||
|
|
|
| |||
S Some localities are adopting sound ordinances based | threaded adapter. |
| ||||
on the unit’s sound level registered from the adjacent | NOTE eep the height of ext | enders short enough to | ||||
property, not from the installation property. Install the | ||||||
ensure a sturdy installation. If it is necessary to extend | ||||||
unit as far as possible from the property line. | further, consider a different type of field−fabricated | |||||
|
|
|
| |||
S When possible, do not install the unit directly outside | framework that is sturdy enough for greater heights. | |||||
a window. Glass has a very high level of sound | ROOF MOUNTING |
| ||||
transmission. For proper placement of unit in relation |
| |||||
|
| |||||
to a window see the provided illustration in figure 5, | Install the unit a minimum of 6 inches (152 mm) above the | |||||
detail A. | roof surface to avoid ice build−up around the unit. Locate | |||||
|
|
|
| the unit above a load bearing wall or area of the roof that | ||
PLACING UNIT ON SLAB | can adequately support the unit. Consult local codes for | |||||
When installing unit at grade level, the top of the slab | rooftop applications. See figure 5, detail F for other roof top | |||||
should be high enough above grade so that water from | mounting considerations. |
| ||||
|
|
|
|
| ||
CLEARANCE ON ALL SIDES | MINIMUM CLEARANCE | |||||
| ABOVE UNIT | |||||
|
|
|
|
| ||
|
|
| NOTES: |
|
| |
|
|
|
|
| ||
|
|
|
|
|
S Service clearance of 30 inches (762 mm) must be maintained on one of the sides adjacent to the control panel
S Clearance to one of the other three sides must be 36
inches (914mm).
48 (1219)
S Clearance to one of the remaining two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).
CONTROL PANEL ACCESS
LOCATION
MINIMUM CLEARANCE BETWEEN TWO UNITS
24
(610)
Figure 4. Installation Clearances
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Page 7
XP13 SERIES