Refrigerant Line Sets: Installing Vertical Runs (new construction shown)
NOTE: Similar installation practices | Outside Wall | |
| ||
should be used if line set is to be | Wood Block | |
installed on exterior of outside wall. | ||
Between Studs | ||
|
Vapor Line Wrapped with Armaflex
Liquid Line
Outside Wall
IMPORTANT:
Refrigerant lines must not contact structure.
Caulk
IMPORTANT: Refrigerant lines must not contact wall.
Vapor Line Liquid Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wood Block
Wire Tie
Strap
PVC Pipe Fiberglass
Insulation
Sleeve
Figure 8
3.Use silver alloy brazing rods (5% or 6% silver alloy for
4.Remove the Schrader core assemblies before brazing to protect them from damage due to extreme heat. Replace the cores when brazing is complete.
5.Wrap a wet cloth around the valve body and copper tube stub to protect them from heat damage during brazing.
6.Braze the line set to the service valve. Quench the joints with water or a wet cloth to prevent heat damage to the valve core and opening port. The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing, and rigidity.
7.Install the
Page 6
Refrigerant Metering Device
2SCU13 units are designed for use with either fixed orifice or TXV systems. Refer to the appropriate following section for information on installing the chosen refrigerant meter- ing device.
Fixed Orifice Systems
2SCU13 units are shipped with a fixed orifice refrigerant metering device. Replace the existing indoor unit fixed orifice with the orifice supplied with this unit. Place the supplied fixed orifice sticker on the indoor cabinet after installation. See Table 3 for the proper fixed orifice size for each unit. In nonstandard applications, the provided fixed orifice may not be appropriately sized.
Install the fixed orifice as shown in Figure 9. Do not twist cap tubes when loosening the seal nut from the orifice housing. Use wrench to back up the distributor.
Expansion Valve Systems
Expansion valves equipped with
# 48283B006