Lennox International Inc 2SCU13 Slab Mounting, Wind Barrier Construction, Thermostat Designations

Models: 2SCU13

1 18
Download 18 pages 46.65 Kb
Page 3
Image 3
Slab Mounting

Slab Mounting

Discharge Air

Building

Structure

Mounting Slab

Ground Level

2° or 2" per 5' slope tolerance away from building structure.

Figure 2

Wind Barrier Construction

Prevailing Winter Winds

 

Wind Barrier

 

Inlet Air

24"

 

 

Inlet Air

Inlet Air

 

Figure 3

Electrical Wiring

All field wiring must be done in accordance with the National Electrical Code (NEC) recommendations, Canadian Electrical Code (CEC) and CSA Standards, or local codes, where applicable.

Wind Barrier ConstructionThermostat Designations WARNING

Unit must be grounded in accordance with national and local codes. Failure to ground unit properly can result in personal injury or death.

Refer to the furnace or blower coil Installation Instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size.

# 48283B006

1.Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring.

2.Ground unit at unit disconnect switch or to an earth ground. To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting. Units are approved for use only with copper conductors. 24V Class II circuit connections are made to the low voltage pigtails. A complete unit wiring diagram is located inside the unit control box cover (see also pages 16 and 17 of this instruction).

3.Install room thermostat on an inside wall that is not subject to drafts, direct sunshine, or other heat sources.

4.Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit (see Figure 4).

5.Do not bundle any excess 24V control wire inside control box. Run control wire through installed wire tie and tighten wire tie to provide low voltage strain relief and to maintain separation of field-installed low and high voltage circuits.

Thermostat Designations

Thermostat

Indoor Unit

 

R

Power

R

Outdoor

 

Unit

 

Heat

 

W1

W

 

 

 

Y

Cooling

Y

Y1 Outdoor Unit

 

 

G

Indoor Blower

 

 

G

 

C

 

C

C Outdoor Unit

 

 

See unit wiring diagram for power supply connections. If the indoor unit is not equipped with a blower relay, one must be field supplied and installed.

Do not connect C (common) connection between indoor unit and thermostat except when required by the indoor thermostat. Refer to thermostat installation instructions. C (common) connection between indoor unit and outdoor unit required for proper operation.

Figure 4

Refrigerant Piping

Field refrigerant piping consists of liquid and suction lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections).

Select line set diameters from Table 2 on page 4 to ensure that oil returns to the compressor. Size vertical

Page 3

Page 3
Image 3
Lennox International Inc 2SCU13 warranty Slab Mounting, Wind Barrier Construction, Thermostat Designations