Lennox International Inc 81M26, 81M28 INSTALLER settings continued, Energy Efficient Recovery

Models: 81M26 81M27 81M28

1 28
Download 28 pages 35.57 Kb
Page 23
Image 23
ENERGY EFFICIENT RECOVERY

110-1052F 5/12/05 11:59 AM Page 23

INSTALLER settings (continued)

ENERGY EFFICIENT

RECOVERY

DISABLE

ENABLE

USER MENU

SELECT

DEADBAND SETPOINT

3˚F

ENERGY EFFICIENT RECOVERY

When turned on, the thermostat will look up to two hours before the next event and anticipate when to turn on to reach the desired temperature.

NOTE: This will not allow the second stage to turn on until 20 minutes before the event.

DEADBAND SETPOINT

Deadband is used only when the AUTO CHANGEOVER feature is enabled. The deadband is the temperature difference between the heating and cooling setpoints. This is adjustable from 3-8°F (2.0-4°C).

USER MENU

SELECT

HUMIDITROL

DISABLE

ENABLE

INSTALL MENU

SELECT

ENTER SECURITY CODE

FOR INSTALLER

SETTINGS

0 0 0 0

HUMIDITROL

If the HUMIDITROL accessory is present in the HVAC equipment, this feature should be enabled. Otherwise, it should be disabled.

SECURITY CODE

Enter a code to prevent changes to the INSTALLER settings.

USER MENU

SELECT

23

Page 23
Image 23
Lennox International Inc 81M26, 81M28, 81M27 user manual INSTALLER settings continued, Energy Efficient Recovery