
Healthy Climate® Dealer Installation Instructions
Forced air handler/furnace system with an HRV/ERV
This application provides filtration of all Outdoor Air (OA) that is brought into the home through the HRV/ERV, thus reducing the introduction of dust, pollen and mold from the outdoor air. For systems that have HRV/ERV units installed, we recommend ducting the ‘fresh air’ outlet from the HRV/ERV into the HEPA system. If the HRV/ERV CFM (cubic feet per minute) rating is lower than that of the HEPA system, an additional return needs to be installed into the HEPA system (See figure 8.) The output air from the HEPA system then needs to be installed into the main return of the air handler/furnace system.
Preparation: |
|
|
|
| Example of Return | ||
|
|
|
| to Return Installation | |||
Here are some things to consider as you |
|
|
|
| with an HRV/ERV | ||
decide where to install the HEPA system |
|
|
|
| |||
/ERV |
|
| For homes with a forced | ||||
with an HRV/ERV. |
|
| |||||
|
|
|
| air handler/furnace sys- | |||
|
|
|
|
|
| ||
Location: |
|
|
|
| tem and an HRV/ERV | ||
|
|
|
| system. | |||
• | Make sure there is room to open the |
|
|
|
| ||
|
|
|
| Additional Return | |||
| HEPA filter access panel for filter |
|
|
|
| ||
| changes/inspections. |
|
|
|
| Air Handler/Furnace | |
|
|
|
|
| |||
• | Keep the HEPA system in a location |
|
|
|
| Air Handler/Furnace Filter | |
| where you can still access the air han- |
|
|
| Figure 8. | HEPA System | |
| dler/furnace filter. |
|
|
|
| ||
|
|
|
|
|
| ||
• Keep the HEPA system away from pos- | NOTE: This filtration system is an ADDITIONAL filter, and does NOT | ||||||
| sible water damage | replace the existing air handler/furnace system filter. | |||||
• | Vibration pads will reduce vibration for | ||||||
|
|
|
|
| |||
|
| • | Each connection must be sealed with aluminum | ||||
| installations where the unit is placed on |
|
| ||||
| the floor. |
|
|
| tape or mastic, including all take offs. | ||
• | Install HEPA System on floor or suspended platform. | • | Installed duct runs should be as straight as possible | ||||
| If the unit is suspended, screws must not penetrate |
| (if the duct runs are too long, reduced CFM may | ||||
| through the cabinet. Make sure that you have the |
| result). |
| |||
| proper chains/straps/joists and equipment to keep | • | If duct is exposed to unconditioned air, externally | ||||
| unit secure. |
|
|
| insulated flex duct is highly recommended. | ||
Inlet (Marked as ‘Air In’ on unit): |
|
| • | Externally insulated flex duct can also be used for | |||
• Most HRV/ERV systems will not move as much air |
| noise reduction purposes | |||||
| as the HEPA system. For these systems, install an | • | For best indoor air quality, do not use ductboard or | ||||
| additional return from another treated air source |
| fiberglass inside of ducts. | ||||
| into the HEPA system. |
|
| Electricity: |
| ||
• | If using an additional return duct, it should be | • | The unit must be plugged into a grounded 120V, | ||||
| installed upstream of any humidifiers. The fresh |
| 60Hz outlet. |
| |||
| air outlet of the HRV/ERV should be “Y” connected | Required Materials for Installation of Unit: | |||||
| to the additional return duct then connected to the | ||||||
| inlet of the HEPA system. |
|
| For Model: |
| ||
• | The additional return duct (if any) should be | 8” diameter flex or rigid duct (as required) | |||||
| installed at least 8 ft. away from the outlet duct on | 6” diameter flex or rigid duct (as required) | |||||
| the main return. |
|
| 6” diameter 45 degree takeoff | |||
• | Duct both the HRV/ERV and the additional return | Aluminum tape or mastic | |||||
| into the inlet of the HEPA system. |
|
| Misc. hanging materials - field provided | |||
Outlet (Marked as ‘Clean Air Out’ on unit): |
|
| For Models: | ||||
• | Outlet duct should be installed as close to the air | 10” diameter flex or rigid duct (as required) | |||||
| handler/furnace inlet as possible but not directly into | 8” diameter flex or rigid duct (as required) | |||||
| the return air elbow of the main return. |
|
| 10” diameter 45 degree takeoff | |||
• | To reduce static pressure, install outlet with a 45 | 8” diameter 45 degree takeoff | |||||
| degree takeoff directly | Aluminum tape or mastic | |||||
| of air handler/furnace. |
|
| Misc. hanging materials - field provided | |||
Ducting: |
|
| NOTE: Be sure to review ‘Rules for Safe Installation | ||||
• | If HEPA system is installed where inlet and outlet | ||||||
| collars face down, metal elbows must be connected | and Operation’ on page 1 of this document before | |||||
| to both inlet and outlet collars. |
|
|
|
10