Lennox International Inc EL280DF installation instructions Proper Combustion, High Altitude

Models: EL280DF

1 32
Download 32 pages 56.09 Kb
Page 26
Image 26
Proper Combustion

Proper Combustion

Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com- bustion. Table 12 shows acceptable combustion for ALL EL280DF models. The maximum carbon monoxide reading should not exceed 50 ppm

TABLE 12

Firing Rate

CO2% For Nat

CO2% For L.P.

High Fire

6.8 − 7.4

7.5 − 9.0

 

 

 

Low Fire

4.2 − 5.7

5.0 − 6.0

 

 

 

High Altitude

The manifold pressure may require adjustment and com- bustion air pressure switch may need replacing to ensure proper combustion at higher altitudes. Refer to table 13 for

manifold pressure and table 14 for pressure switch change and gas conversion kits.

High AltitudeIMPORTANT

For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.

TABLE 13

Manifold Pressure Settings at all Altitudes

 

 

Manifold

Manifold

Manifold

Supply Line

Unit

Gas

Pressure in.wg.

Pressure in.wg.

Pressure in.wg.

Pressure

0−4500 ft.

4501−7500 ft.1

7501 − 10,000 ft.2

in. w.g.

Input

 

 

 

 

 

 

 

 

 

 

 

Low Fire

High Fire

Low Fire

High Fire

Low Fire

High Fire

Min

Max

 

 

 

 

 

 

 

 

 

 

 

Natural

1.7

3.5

1.5

3.2

1.7

3.5

4.5

13.0

070

 

 

 

 

 

 

 

 

 

LP/propane3

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

 

Natural

1.7

3.5

1.5

3.0

1.7

3.5

4.5

13.0

090

 

 

 

 

 

 

 

 

 

LP/propane3

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

 

Natural

1.7

3.5

1.5

3.2

1.7

3.5

4.5

13.0

110

 

 

 

 

 

 

 

 

 

LP/propane3

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

1This is the only permissible derate for these units.

2Natural gas high altitude orifice kit required.

3A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

NOTE − Units may be installed at altitudes up to 4500 ft. above sea level without modifications.

TABLE 14

Pressure Switch and Gas Conversion Kits at all Altitudes

 

High Altitude Pressure Switch Kit

High Altitude

LP/Propane Gas Kit

LP/Propane to

Unit

Natural Gas Kit

Natural Kit

 

 

 

 

 

Input

 

 

 

 

 

 

 

0 − 4500 ft.

4501 − 7500 ft.

7501 − 10,000 ft.

7501 − 10,000 ft.

0 − 7500 ft

7501 − 10,000 ft.

0 − 7500 ft.Min

 

 

 

 

 

 

 

 

 

070

 

 

73W36

 

 

 

 

 

 

 

 

 

 

 

 

090

No Change

No Change

73W36

73W37

77W07

77W11

77W09

 

 

 

 

 

 

 

 

110

 

 

73W35

 

 

 

 

 

 

 

 

 

 

 

 

NOTE − A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

Page 26

Page 26
Image 26
Lennox International Inc EL280DF installation instructions Proper Combustion, High Altitude