Service

WARNING

ELECTRICAL SHOCK, FIRE,

OR EXPLOSION HAZARD.

Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.

Improper servicing could result in dangerous opera- tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace.

When servicing controls, label all wires prior to dis- connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.

At the beginning of each heating season, a qualified techni- cian should check the system as follows:

Blower

Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.

WARNING

The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju- ry or death.

Filters

All ML180UHE filters are installed external to the unit. Fil- ters should be inspected monthly. Clean or replace the fil- ters when necessary to ensure that the furnace operates properly. Replacement filters must be rated for high veloc- ity airflow. Table 1 lists recommended filter sizes.

Flue And Chimney

1 − Check flue pipe, chimney and all connections for tight- ness and to make sure there is no blockage.

2 − Check unit for proper draft. Electrical

1 − Check all wiring for loose connections.

2 − Check for the correct voltage at the furnace (furnace operating). Correct voltage is 120VAC + 10%.

3 − Check amp−draw on the blower motor with blower ac- cess panel in place.

Unit Nameplate__________Actual__________

Cleaning the Heat Exchanger and Burners

NOTE − Use papers or protective covering in front of the fur- nace during cleaning.

1 − Turn off both electrical and gas power supplies to fur- nace.

2 − Remove flue pipe and top cap (some applications top cap can remain) from the unit.

3 − Label the wires from gas valve, rollout switches, prima- ry limit switch and make−up box then disconnect them.

4 − Remove the screws that secure the combustion air in- ducer/pressure switch assembly to the collector box. Carefully remove the combustion air inducer to avoid damaging blower gasket. If gasket is damaged, it must be replaced to prevent leakage.

5 − Remove the collector box located behind the combus- tion air inducer. Be careful with the collector box gas- ket. If the gasket is damaged, it must be replaced to prevent leakage.

6 − Disconnect gas supply piping. Remove the four screws securing the burner manifold assembly to the vestibule panel and remove the assembly from the unit.

7 − NOX units only − Remove screw securing NOX insert. Remove NOX insert. See figure 38.

8 − Remove screws from both sides, top and bottom of vestibule panel.

9 − Remove heat exchanger. It may be necessary to spread cabinet side to allow more room. If so, remove five screws from the left side or right side of cabinet. See figure 39.

10 −Backwash using steam. Begin from the burner opening on each clam. Steam must not exceed 275°F.

11− To clean burners, run a vacuum cleaner with a soft brush attachment over the face of burners. Visually inspect in- side the burners and crossovers for any blockage caused by foreign matter. Remove any blockage. Figure 37 shows burner detail.

12−To clean the combustion air inducer visually inspect and using a wire brush clean where necessary. Use com- pressed air to clean off debris and any rust.

13−Reinstall heat exchanger in vestibule. (Replace the five screws in the cabinet from step 10 if removed).

14−NOx units only − Replace NOx inserts.

15−Reinstall collector box and combustion air assembly. Reinstall all screws to the collector box and combustion air inducer. Failure to replace all screws may cause leaks. Inspect gaskets for any damage and replace if necessary.

16−Reinstall burner box and manifold assembly.

17−Reconnect all wires.

18−Reconnect top cap and vent pipe to combustion air in- ducer outlet.

19−Reconnect gas supply piping.

20−Turn on power and gas supply to unit.

21−Set thermostat and check for proper operation.

22−Check all piping connections, factory and field, for gas leaks. Use a leak detecting solution or other preferred means.

23−If a leak is detected, shut gas and electricity off and repair leak.

24−Repeat steps 24 and 26 until no leaks are detected.

25−Replace access panel.