Integrated Control Diagnostic Codes

RED LED

Diagnostic Codes / Status of Furnace

Flash Code

 

 

 

Off

No power to control or board fault detected

 

 

On

Board fault detected,

 

 

Heartbeat1

Control powered − displayed during all modes of operation if no errors are detected

1

Reverse Line Voltage Polarity

 

 

2

Improper Earth Ground

 

 

3

Burner failed to light, or lost flame during heat demand

 

 

4

Low Flame Signal − check flame sensor

 

 

5

Watchguard − burner failed to light, exceeded maximum number of retries or recycles.

 

 

6

Not Used

 

 

7

Primary or Secondary Limit Open or Watchguard Mode − Limit Switch Open longer than 3 min-

utes

 

 

 

8

Rollout Switch Open

 

 

9

Pressure Switch failed to close or opened during heat demand

 

 

10

Watchguard − Pressure Switch opened 5 times during one heat demand

 

 

11

Pressure Switch stuck closed prior to activation of combustion air inducer

 

 

12

Flame Sensed without gas valve energized

 

 

13

Low Line Voltage

 

 

 

Notes

 

 

Note 1

A "Heartbeat" is indicated by a "Slow Flash" − 1 sec on 1 sec off, repeating

 

 

Note

Error codes are indicated by a "Rapid Flash" − the LED flashes X times at 1/2 sec on 1/2 sec

off, remains off for 3 sec, then repeats

 

 

 

 

Last 10 error codes are stored in memory including when power is shut off to the unit. − To recall,

Note

press and release button, most recent will be displayed first, LED off for 3 sec, then next error

 

code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.

 

 