Chapter 7 Buffer read/write instructions
7 - 6
7.2 Buffer write instructions

7.2.1 PUT / PUTP instructions

PUT, PUTP FUN(234) PUT
FUN(235) PUTP Applicable CPU
K200S
K300S
K1000S
Available devices Flag
Instructions M P K L F T C S D #D Integer Steps Error
(F110) Zero
(F111) Carry
(F112)
n1 ¡
S ¡
D ¡ ¡ ¡ ¡* ¡ ¡ ¡ ¡
PUT
PUTP
n2 ¡
9 ¡
Operand setting
n1 Slot number at which A/D
module is mounted
D Start address of buffer memory
at which data will be written
D Start address of source data of
CPU module
n2 Number of word to be written
* Available only when do not use computer link module or data link module
1) Functions
Write the data of n2 words, which start at the address specified as S of CPU, and
transfer the data into the block starting at the address specified as D of buffer memory
inside the A/D module mounted at the slot number n1.
Buffer memory
of A/D module CPU module
[ D ] [ S ]
[ D+n2-1 ]
n2 words
[ S+n2-1 ]
n2 words
PUT(P) n1 D S n2
Input
condition