Chapter 7 Buffer read/write instructions
7 - 10
2) Program example
- Program that write 10 words, through the Fnet module mounted at the slot 02, from the
D0200 ~ D0209 of self station to the address 11~20 of the buffer memory of the G3F-
AD3A module mounted at the slot 02 of remote station h0E. The link status will be stored
at M020 of self station.
[ System configuration ]
Self-station
GM4-
PA2A K4P-
15AS G4I-
D22A G4I-
D22A G4L-
FUEA
Station
No=h01
G4L-
FUEA
Station
No=h02
G4Q-
RY2A
slot 0 slot 1 slot 2 slot 3 slot 4
Remote station
GM3-
PA2A G3L-
RBEA
Station
No=h0E
G3I-
D22A G3Q-
RY2A G3F-
AD3A
slot 0 slot 1 slot 2
[ Example program ]
sl : upper byte à the code of remote module is hC0
lower byte à slot number of Fnet module of self station is h02
st : upper byte à slot number of remote A/D module is h02
lower byte à the station number of remote station is h0E
RPUT hC002 h020E D0200 00011 0010 M020
Input
condition