LG Electronics K4F-PIDA, K7F-PIDA manual General Specifications, General specifications

Models: K4F-PIDA K7F-PIDA

1 40
Download 40 pages 56.02 Kb
Page 8
Image 8

Chapter 2. SPECIFICATIONS

Chapter 2 . SPECIFICATIONS

2.1General Specifications

Table 2.1 shows the general specifications of MASTER-K series.

No

Items

Specifications

Standard

 

 

 

 

 

1

Operating ambient

0 ~ 55￿

 

temperature

 

 

 

 

 

2

Storage ambient

-25 ~ 70￿

 

temperature

 

 

 

 

 

3

Operating ambient

5 ~ 95%RH,

non-condensing

 

humidity

 

 

 

 

 

4

Storage ambient

5 ~ 95%RH,

non-condensing

 

humidity

 

 

 

 

 

 

 

Occasional vibration

 

5

6

 

Frequency

Acceleration

Amplitude

Sweep count

 

 

10￿f￿57 Hz

-

0.075 mm

 

 

 

Vibration

57 ￿f￿150 Hz

9.8￿ {1G}

-

10 times in each

 

IEC 1131-2

 

Continuous vibration

 

 

 

direction for

 

 

 

Frequency

Acceleration

Amplitude

X, Y, Z

 

 

 

10￿f￿57 Hz

-

0.035 mm

 

 

 

 

 

 

 

57￿f￿150 Hz

4.9￿ {0.5G}

-

 

 

 

Shocks

*Maximum shock acceleration: 147

￿ {15G}

 

 

IEC 1131-2

*Duration time :11 ms

 

 

 

 

*Pulse wave: half sine wave pulse( 3 times in each of X, Y and Z directions )

 

7

 

Square wave impulse noise

 

￿1,500 V

 

 

 

 

 

 

 

 

 

 

Electrostatic discharge

Voltage :4kV(contact discharge)

IEC 1131-2

 

IEC 801-2

 

 

 

 

 

 

 

Radiated electromagnetic field

 

27 ~ 500 MHz, 10 V/m

IEC 1131-2

 

 

IEC 801-3

Noise immunity

 

 

 

 

 

 

 

 

Digital

Digital I/Os

 

 

 

 

 

 

 

 

Severity

All power

I/Os

(Ue < 24 V)

 

 

 

( Ue

Analog I/Os

IEC 1131-2

 

Fast transient burst noise

Level

modules

 

communication

IEC 801-4

 

 

 

 

 

 

 

 

24 V)

I/Os

 

 

 

 

 

 

 

 

 

 

Voltage

2 kV

1 kV

0.25 kV

 

8

Operating atmosphere

Free from corrosive gases and excessive dust

 

 

 

 

 

9

Altitude for use

Up to 2,000m

 

 

 

 

 

10

Pollution degree

2 or lower

 

 

 

 

 

11

Cooling method

Self-cooling

 

 

 

 

 

[Table 2.1 ] General specifications

REMARK

1)IEC(International Electrotechnical Commission)

:The international civilian organization which produces standards for electrical and electronics industry.

2)Pollution degree

:It indicates a standard of operating ambient pollution level.

The pollution degree 2 means the condition in which normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected.

2 - 1