Installation
PipingLengthAndElevation
Capacity | Pipe Size | Standard | Max. | Max. | Additional Refrigerant | ||
|
| Length | Elevation | length | |||
(Btu/h) | Suction | Evap | m(ft) | B m(ft) | A m(ft) | g/m(oz/ft) | |
| |||||||
|
|
|
|
|
|
| |
9k | 3/8" | 1/4" | 7.5(25) | 7.5(25) | 15(49) | 20(0.22) | |
1/2" | 1/4" | 7.5(25) | 7.5(25) | 15(49) | 20(0.22) | ||
| |||||||
12k | 1/2" | 1/4" | 7.5(25) | 7.5(25) | 15(49) | 20(0.22) | |
18k | 1/2" | 1/4" | 7.5(25) | 15(49) | 30(98) | 20(0.22) | |
5/8" | 1/4" | 7.5(25) | 7.5(25) | 15(49) | 20(0.22) | ||
| |||||||
24k | 5/8" | 1/4" | 7.5(25) | 7.5(25) | 15(49) | 20(0.22) |
Indoor unit
B
A
Outdoor unit
A
Indoor unit
Outdoor unit |
| Outdoor unit |
| Oil trap | A |
|
| |
B | Indoor unit | B |
|
In case more than 5m(16.4ft)
•Capacity is based on standard length and maximum allowance length is on the basis of reliability.
•Oil trap should be installed every 5~7meters (16.4~23.0ft).
14Room Air Conditioner