Technical data
| |
EMC directive | 89/336/EWG |
Immunity | EN |
Emissions | EN |
Low voltage directive | 73/23/EWG |
Safety | EN |
Rated operating voltage | AC 230 V |
Frequency | 50 Hz |
Power consumption | 8 VA |
Degree of protection (cover closed) | IP42 EN 60529 |
Safety class | II EN 60730 |
Output relays |
|
Rated voltage | AC 230 V |
Rated current | 2 (2) A |
Contact current at AC 24...90 V | 0.1...2 A, cos ϕ >0.6 |
Contact current at AC 90...250 V | 0.02...2 A, cos ϕ >0.6 |
Rated current of ignition transformer | max. 1 A during max. 30 s |
max. 10 A during max. 10 ms | |
Perm. ambient temperature |
|
Transport and storage | |
Operation | 0...50 °C |
Perm. cable lengths to the sensors and external |
|
contacts |
|
Copper cable 0.6 mm dia. | 20 m |
Copper cable 1.0 mm2 | 80 m |
Copper cable 1.5 mm2 | 120 m |
Perm. cable lengths to the room unit |
|
Copper cable 0.25 mm2 | 25 m |
Copper cable from 0.5 mm2 | 50 m |
Bus loading characteristic E (LPB) | 6 |
Backup of time switch | 12 h min. |
Weight (net) | 1.1 kg |
Connection diagrams Basic connections on the low voltage side
AC 230 V
S2 |
LPB
D1 D2
L |
|
|
|
|
|
|
|
|
|
|
|
|
| B9 |
|
| B7 | H2 | B5 |
N
2527A01
Basic connections on the mains voltage side
AC 230 V
2527A02
A6 | Room unit QAW50 or QAW70 | M1 | Heating circuit pump |
B1 | Flow sensor | N1 | Controller RVL469 |
B5 | Room sensor | S1 | Remote control operating mode |
B7 | Return sensor | S2 | Remote control flow temperature setpoint |
B9 | Outside sensor | Y1 | Actuator heating circuit |
LPB | Data bus |
|
|
CE1N2527E / 04.03.1999 | Siemens Building Technologies |
6/8 | Landis & Staefa Division |