8 - Calibrations
The air conditioner has already been
For the MICROFACE calibrations refer to the rele vant manual (to avoid wrong operations do not use
temperature and rel. humidity set points/propor tional bands which differ excessively from the stan dard settings).
COMPONENT |
| Setting (LP) | NOTES | |
|
|
|
| |
Low pressure | STOP | : 1.2 bar | automatic | |
START | : 2 bar | |||
switch (LP) | reset | |||
(fixed settings) | ||||
|
| |||
|
|
|
| |
|
|
| manual reset | |
High pressure | STOP | : 26 bar | pressing the | |
START | : 20 bar | push button | ||
switch (HP) |
| |||
(fixed settings) |
| |||
|
| |||
|
|
|
|
Fan | START | : 18 bar | ||
DIFF | : | 4 bar | ||
pressure switch | ||||
(STOP | : | 14 bar) | ||
(SP) | ||||
(fixed settings) | ||||
|
| SET. | : | 16 bar | |
Fan speed | BAND P | : | 3.5 bar | |
(For the adjustment refer | ||||
adjuster | ||||
to the instructions supplied | ||||
| ||||
| with the machine) |
English | page 8 | 272014 - 04.02.2000 |
|
|
|