8 - Calibrations

￿The air conditioner has already been factory-tested and calibrated as described below.

￿For the MICROFACE calibrations refer to the rele￿ vant manual (to avoid wrong operations do not use

temperature and rel. humidity set points/propor￿ tional bands which differ excessively from the stan￿ dard settings).

COMPONENT

 

Setting (LP)

NOTES

 

 

 

 

Low pressure

STOP

: 1.2 bar

automatic

START

: 2 bar

switch (LP)

reset

(fixed settings)

 

 

 

 

 

 

 

 

 

manual reset

High pressure

STOP

: 26 bar

pressing the

START

: 20 bar

push button

switch (HP)

 

(fixed settings)

 

 

 

 

 

 

 

Fan

START

: 18 bar

DIFF

:

4 bar

pressure switch

(STOP

:

14 bar)

(SP)

(fixed settings)

 

 

SET.

:

16 bar

Fan speed

BAND P

:

3.5 bar

(For the adjustment refer

adjuster

to the instructions supplied

 

 

with the machine)