1 - Preliminary operations
1.1 - Foreword
The following manual describes the installation, opera tion and maintenance of Air Conditioners, series Hiline Slim (see Fig. 1).
IMPORTANT:
Also consult the manual for the Microface microproces sor control supplied with the machine (if installed).
1.2 - Operating limits
The units are designed to operate within working ranges (see Tab. 1).
These limits are referred to new machines or for those that have been correctly installed and serviced.
The warranty clauses are no longer valid for any damage or malfunction that may occur during or due to opera tion outside the application values.
Tab. 1 - Operating limits
|
| 230 V 10%/1/50 Hz | |
Power supply voltage |
|
| |
24/48 30% Vdc with INVERTER | |||
| |||
|
|
| |
| da: | ||
Outdoor conditions |
|
| |
a: | 43C | ||
| |||
|
|
| |
Indoor conditions with | da: | 20C 30% R.H. e 20C 80% | |
| R.H. | ||
|
| ||
operating compressor |
|
| |
a: | 35C, 40% R.H. | ||
| |||
|
|
| |
| da: | ||
Storage conditions |
|
| |
a: | 55C, 90% R.H. | ||
| |||
|
|
| |
External side protection |
| IP 24 | |
degree |
| ||
|
| ||
|
|
|
1.3 - Sound pressure levels
Tab. 2 shows, for the internal and the external side, the maximum sound pressure levels of the units in standard configuration, in continuous operation, at 2 m from the front surface of the machine, at 1 m height in free field conditions. The noise levels have the highest values at the front of the unit, on the internal side.
1.4 - Sealing the room
To create stable indoor conditions make sure that the
room is airtight by sealing all gaps, cable entries, etc...
1.5 - Inspection
On receiving the equipment immediately inspect its condition; report any damage to the transport company at once.
1.6 - Transport
Always keep the unit vertically upright.
If possible transport the unit using a fork lift truck; otherwise use a crane with belts or cables, avoiding the exerting of pressure on the top edges of the pack ing.
Unpack the unit as close as possible to its installation position. Once unpacked, avoid stress being trans mitted to its internal components.
1.7 - Positioning of air conditioner
The air conditioner can be installed in any indoor location where it is not exposed to an aggressive ambient.
Position the air conditioner so as to ensure optimum air distribution within the area in which it is to oper ate, preventing the creation of unconditioned zones.
For the correct positioning of the air conditioner see Fig. 2 at the end of the manual.
1.8 - Service area
The unit must be provided with a suitable Service Area, as follows (see Fig. 2):
All ordinary maintenance can be performed both from the front side and from the rear side (external) where a minimum area must be left free of obstruc tions.
1.9 - Wall holes
Make the holes in the wall of the container next to the unit's position (see Fig. 3).
English | page 2 | 272014 - 04.02.2000 |
|
|
|