Liebert 700-2200 VA Rackmount Specifications, DIMENSIONS in mm, WEIGHT lbs kg, Environmental

Models: 700-2200 VA

1 26
Download 26 pages 5.06 Kb
Page 24
Image 24
RACKMOUNT SPECIFICATIONS

RACKMOUNT SPECIFICATIONS

Model Number

PS700RM-120

 

PS1000RM-120

PS1400RM-120

 

PS2200RM-120

Model Rating VA/W

700 / 450

 

1000 / 670

1400 / 950

 

2200 / 1600

DIMENSIONS: in (mm)

 

 

 

 

 

 

Unit

19 x 18 x 5.25

 

19 x 18 x 5.25

19 x 18 x 5.25

 

19 x 18 x 7

W x D x H

(483 x 457 x 133)

 

(483 x 457 x 133)

(483 x 457 x 133)

 

(483 x 457 x 178)

 

 

 

 

 

 

Shipping

27.5 x 24 x 11

 

27.5 x 24 x 11

27.5 x 24 x 11

 

27.5 x 24 x 12

W x D x H

(699 x 610 x 279)

 

(699 x 610 x 279)

(699 x 610 x 279)

 

(699 x 610 x 305)

 

 

 

 

 

 

WEIGHT: lbs (kg)

 

 

 

 

 

 

Unit

41.5 (18.9)

 

51.29 (23.3)

57.2 (26.0)

 

86.0 (39.1)

Shipping

50.82 (23.1)

 

59.85 (27.2)

66.1 (30.0)

 

95.3 (43.3)

INPUT AC PARAMETERS

 

 

 

 

 

 

Voltage Range

 

 

120 VAC; -25%, +23%

 

Voltage Raise

Maintains output to 120 VAC; -14%, when input is 120 VAC, -25%

Voltage Lower

Maintains output to 120 VAC; +10%, when input is 120 VAC, +23%

Frequency

 

 

45-55 Hz or 55-65 Hz; auto sensing

 

Input

6 ft. detachable, w/

 

6 ft. attached, w/

6 ft. attached, w/

 

6 ft. attached, w/

Power Cord

NEMA 5-15 P

 

NEMA 5-15 P

NEMA 5-15 P

 

NEMA L5-30 P

 

 

 

 

 

 

OUTPUT AC PARAMETERS

 

 

 

 

 

Output Receptacles

(6) 5-15R

 

(6) 5-15R

(6) 5-15R

 

(6)5-15R (2)5-20R

Voltage

 

 

103 VAC

to 132 VAC

 

 

Max. Current Rating

5.8 A

 

8.3 A

11.67 A

 

18.3 A

Frequency

 

 

50 Hz or 60 Hz

 

Waveform

 

 

Sinewave

 

Utility Mode Overload

 

200% for > 2 cycles; 110% for > 5 minutes

Battery Mode Overload

150% for > 1 cycle; 110% for > 30 seconds

BATTERY PARAMETERS

 

 

 

 

 

 

Type

 

 

Valve-regulated, nonspillable, lead acid

 

Qty. x Voltage x Rating

2 x 12V x 7.0 or 7.2 AH

 

3 x 12V x 7.0 or 7.2 AH

4 x 12V x 7.0 or 7.2 AH

 

8 x 6V x 12 AH

 

 

 

 

 

 

 

 

 

Batt. Mfg./ Part Number

CSB: GP1270F2 or Panasonic LC-R127R2CH1

 

Panasonic:

 

 

 

 

 

 

LC-R0612CH1

Transfer Time

 

 

2-6 ms typical

 

 

Back-up Time

 

 

See Typical Battery Discharge Curves

 

Recharge Time

3 Hours

 

3 Hours

5 Hours

 

3 Hours

 

to 95%

capacity, after full

discharge into 100% load

ENVIRONMENTAL

 

 

 

 

 

 

Operating Temperature

 

 

+32° F to + 104° F (0° C to +40° C)

 

Storage Temperature

 

 

+5° F to + 122° F (-15° C to +50° C)

 

Relative Humidity

 

 

0% to 95%, non-condensing

 

Operating Elevation

Up to 10,000 ft. (3000 m) at 35° C without derating

Storage Elevation

 

 

50,000 ft. (15,000 m) maximum

 

Audible Noise

 

 

<45 dBA, at 1 meter

 

AGENCY

 

 

 

 

 

 

Safety

 

 

UL 1778, c-UL Listed

 

RFI/EMI

 

 

FCC Part 15, Subpart B, Class A

 

Immunity

IEC 801-2, Level 4 / IEC 801-4, Level 4 / IEEE 587 Category A

24

Page 24
Image 24
Liebert 700-2200 VA Rackmount Specifications, DIMENSIONS in mm, WEIGHT lbs kg, Output Ac Parameters, Environmental, Agency