Liebert DPN001599 REV 12/11 LIEBERT XD CHILLER XDC WITH iCOM CONTROLS, Model, 50/60 HZ, XDC160

Models: DPN001599 REV 12/11

1 6
Download 6 pages 25.25 Kb
Page 3
Image 3
UNIT PIPING OUTLET CONNECTION SIZES, inches

LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS

To First Cooling Module or Bypass Flow Controller **

22in

559mm

Install Replaceable Filter Drier Assembly in Liquid Supply Line

Return Line From

A Cooling Units

(line is spin closed)

(elbow customer provided)

DIMENSIONS ARE SUBJECT

TO CHANGE WITHOUT NOTICE.

47in

 

1194 mm

44in

~

1118 mm

6in

152 mm

23in

584 mm

21in

533mm

31/4in

83mm

Orientation

Defined by

Installer.*

8in

*

203mm

BLiquid Supply Line

To Cooling Units

C Hot Gas Refrigerant Lines

* Allow 8in (204mm) Of Clearance For Filter Replacement. Filter assembly may be positioned horizontally.

**To Ensure All Refrigerant Flow is Filtered, Install the Filter Drier Assembly Between the Discharge Line of the Liebert XDC and the first Bypass Flow Controller or the first Liebert XD Cooling Module.

DLiquid Refrigerant Lines

UNIT PIPING OUTLET CONNECTION SIZES, inches

MODEL

A

B

C

D

 

50/60 HZ

OD CU

OD CU

OD CU

OD CU

 

 

 

 

 

 

XDC160

2-1/8

1-1/8

1-3/8

7/8

 

 

 

 

 

REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

PAGE 3/6

REV 12/11

 

 

REV 4

Page 3