ELECTRIC CONDUIT KNOCKOUTS

LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS

Three phase electric service not provided by Liebert.

Field supplied disconnect On top of electric box. Knockout sizeFactory installed unit disconnect switchesTwo Liebert Intellislots® for optional OCWEB-LBDS or OC485-LBDS card. switch may not be required,60HZ COMPONENTS SHOWNManual backgroundManual backgroundManual backgroundManual background check local codes.

HEAT REJECTION CONNECTION (R-407C Side)

Three phase electric service

not by Liebert.

Field supplied 24V. Class 1 wiring to

 

interlock heat rejection from pigtails:

ELECTRIC CONDUIT KNOCKOUTS

70A & 71A - Compressor 1 circuit

On top of electric box. Knockout size

70B & 71B - Compressor 2 circuit

2 in (51 mm)

70C & 71C - Dual Cool relay (optional)

 

Electrical handy box factory

 

installed with cover.

 

THREE PHASE CONNECTION

 

Electric service connection terminals

 

Factory wired to components Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background on electric panelManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Factory installed disconnect switch

EARTH GROUND BAR (50Hz only) Connection terminal with factory ground from each high voltage component

Factory installed unit disconnect switches

iCOM display

EARTH GROUND CONNECTION Connection terminal for field supplied earth grounding wire.

CANBUS ISOLATOR

ALARM AND WARNING OUTPUT RELAYS Field supplied 24V Class 2 wire for special alarms.

(Not to exceed 1.0A @ 24v each.)

REMOTE UNIT SHUTDOWN

Replace existing jumper between terminals 37 & 38 with normally closed switch having a minimum 50VA rating. Use field supplied 24V Class 2 wire.

INTELLISLOTS®

Two Liebert Intellislots® for optional OCWEB-LBDS or OC485-LBDS card.

60HZ COMPONENTS SHOWN

NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.

REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

PAGE 5/6

REV 12/11

 

 

REV 4