LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Three phase electric service not provided by Liebert.
Field supplied disconnect switch may not be required, check local codes.
HEAT REJECTION CONNECTION | Three phase electric service | |
not by Liebert. | ||
Field supplied 24V. Class 1 wiring to | ||
| ||
interlock heat rejection from pigtails: | ELECTRIC CONDUIT KNOCKOUTS | |
70A & 71A - Compressor 1 circuit | ||
On top of electric box. Knockout size | ||
70B & 71B - Compressor 2 circuit | ||
2 in (51 mm) | ||
70C & 71C - Dual Cool relay (optional) | ||
| ||
Electrical handy box factory |
| |
installed with cover. |
| |
THREE PHASE CONNECTION |
| |
Electric service connection terminals |
|
Factory wired to components on electric panel
Factory installed disconnect switch
EARTH GROUND BAR (50Hz only) Connection terminal with factory ground from each high voltage component
Factory installed unit disconnect switches
iCOM display
EARTH GROUND CONNECTION Connection terminal for field supplied earth grounding wire.
CANBUS ISOLATOR
ALARM AND WARNING OUTPUT RELAYS Field supplied 24V Class 2 wire for special alarms.
(Not to exceed 1.0A @ 24v each.)
REMOTE UNIT SHUTDOWN
Replace existing jumper between terminals 37 & 38 with normally closed switch having a minimum 50VA rating. Use field supplied 24V Class 2 wire.
INTELLISLOTS®
Two Liebert Intellislots® for optional OCWEB-LBDS or OC485-LBDS card.
60HZ COMPONENTS SHOWN
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
REFER TO
DPN001599 | PAGE 5/6 | REV 12/11 |
|
| REV 4 |