Liebert DPN001599 REV 12/11 LIEBERT XD CHILLER XDC WITH iCOM CONTROLS, To Liebert Xd Cooling

Models: DPN001599 REV 12/11

1 6
Download 6 pages 25.25 Kb
Page 6
Image 6
Liebert XDC Extra Low Voltage field connection points

LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS

Liebert XDC Extra Low Voltage field connection points

TO P64 ON ICOM CONTROL BOARD

 

TO P66 ON ICOM CONTROL BOARD

 

 

 

RED ETHER NET CABLE

 

 

 

 

 

 

TO LIEBERT XD COOLING

 

TERMINATION PLUG

 

 

 

 

 

 

 

 

 

 

MODULE AND REMOTE

 

 

 

 

 

 

T/H SENSOR B

 

 

 

 

 

 

TO REMOTE T/H SENSOR A

 

 

COMMON WARNING OUTPUT

TO OPTIONAL

 

 

 

 

FOR CONTACTS INDICATING AN

EXTERNAL

 

 

ALARM CONDITION.

 

 

CONNECTIONS

 

 

(MAX) 1.0AMP @ 24V

P64

P66

P67

K11

K11

 

 

 

K11NO

K11COM

K11NC

 

 

 

TO REMOTE ALARM

 

 

 

CIRCUIT BY OTHERS

 

 

 

INPUT: REMOTE ALARM DEVICE

 

 

 

FOR INDICATION OF ALARM, WIRE

 

 

 

N.O. CONTACTS FROM REMOTE

UNIT DISPLAY (REAR VIEW)

ALARM DEVICE AS SHOWN.

 

 

 

 

 

 

 

24

 

 

50

FACTORY WIRED

 

 

 

 

 

TEMPERATURE SENSOR.

N.O. CONTACT BY OTHERS

P67

 

 

INPUT: CONDENSATION

 

 

 

DETECTION

DO NOT

 

 

ALARM WHEN CLOSED.

USE

 

 

 

 

 

 

 

 

 

24

 

 

51

 

 

 

N.O. CONTACTS REQUIRED

 

 

1

INPUT: FAN BREAKER STATUS

 

 

 

ALARM WHEN CLOSED.

 

 

 

24

 

 

54

 

 

 

N.O. CONTACTS REQUIRED

 

 

 

COMMON ALARM OUTPUT

 

 

 

FOR CONTACTS INDICATING AN

 

 

 

ALARM CONDITION.

 

 

 

 

 

(MAX) 1.0AMP @ 24V

 

 

 

K3

K3

 

 

 

K3NO

K3COM

K3NC

 

 

 

TO REMOTE ALARM

1

 

 

CIRCUIT BY OTHERS

 

 

INPUT: REMOTE SHUTDOWN

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FOR SHUTDOWN OF CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT, REMOVE JUMPER

1. CONTROL WIRING MUST BE CLASS 2 AND INSTALLED IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BETWEEN TERMINALS 37 & 38

 

ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AND REPLACE WITH N.C. CONTACT

2. REQUIRES SHIELDED CABLE.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

37

38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N.C. CONTACTS BY OTHERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2

REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

PAGE 6/6

REV 12/11

 

 

REV 4

Page 6
Image 6
Liebert DPN001599 REV 12/11 LIEBERT XD CHILLER XDC WITH iCOM CONTROLS, To Liebert Xd Cooling, Module And Remote, External