Liebert PowerSure Personal user manual Communications, Collector to Emitter

Models: PowerSure Personal

1 12
Download 12 pages 30.72 Kb
Page 7
Image 7

COMMUNICATIONS

The PowerSure™ Personal UPS contains a standard DB-9 receptacle located on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:

PIN

ASSIGNMENT DESCRIPTION

 

1

Low Battery (open collector)

 

2

No connection

 

 

3

No connection

 

 

4

On Battery Mode Shutdown (5-12 DC)

 

5

On Battery Mode Shutdown Return

 

6

Utility Fail / Normally On (open collector)

 

7

Low Battery (open emitter)

 

8

Utility Fail (common) (pins 6 & 9)

 

9

Utility Fail / Normally Off (open collector)

 

Pin Assignment

Collector to Emitter*

Open Collector

(+)

(-)

Open Emitter

*Maximum voltage and current on pins 1, 6, 7, 8, 9 is 60V DC; 5.0 mA.

7

Page 7
Image 7
Liebert PowerSure Personal user manual Communications, Collector to Emitter