Liebert Series 600 manual KVA Multi-Module Unit, 208 Volt Standard Module

Models: Series 600

1 95
Download 95 pages 17.52 Kb
Page 93
Image 93

 

 

Table 6

338-500 kVA Multi-Module Unit, 208 Volt - Standard Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Required

Maximum

 

 

 

 

 

 

 

 

* Rectifier

Inverter

Battery

Battery

%

Maximum

 

 

Floor

 

 

 

AC

AC

Discon-

Current

Efficiency

Heat Dis-

Dimen-

Approx.

Loading

UPS

Input

Output

nect

at End of

at

sipation

sions

Weight

Lb./

Rating

Current

Current

Rating

Discharge

Full Load

BTU/hr.

Inches

Lb.

Sq.Ft.

 

 

 

 

 

 

 

 

 

 

Full

 

(Un-

(Distribu-

 

 

 

 

 

 

 

 

 

 

 

ted

kVA

 

kW

Nom

Max

Nom

Max

Amperes

Amperes

 

Load

(WxDxH)

packed)

Loading)

338

 

270

980

1226

937

1171

1000

998

92

91138

128x38x78

8600

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

320

1170

1462

1110

1388

1200

1176

92

101457

218x38x78

10250

214

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

360

1300

1625

1110

1388

1200

1323

92

114140

218x38x78

10250

214

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

400

1462

1827

1388

1735

1600

1470

92

126822

218x38x78

10950

228

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

450

1625

2031

1388

1735

1600

1654

92

142675

218x38x78

10950

228

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable

1,4,5,7,8,

2,5,7,8,

6

6,8,9,

13

13

Notes:

 

9,11,12

9,11,12

 

11,12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For explanation of notes, see referenced numbers in 10.1 - Notes

* Nominal Input Power Factor 0.85 lagging at full load; 9% Maximum Total Input Harmonic Current Distortion (THD) at full load.

 

 

Table 7

338-500 kVA Multi-Module Unit, 208 Volt - Standard Module With Optional Low

 

 

 

 

Distortion Input Filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Rectifier

Inverter

Required

Maximum

%

Maximum

 

 

Floor

 

 

 

Battery

Battery

 

 

UPS

AC

AC

Discon-

Current

Efficiency

Heat Dis-

Dimen-

Approx.

Loading

Input

Output

nect

at End of

at

sipation

sions

Weight

Lb./

Rating

Current

Current

Rating

Discharge

Full Load

BTU/hr.

Inches

Lb.

Sq.Ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

(Distribu-

kVA

 

kW

Nom

Max

Nom

Max

Amperes

Amperes

 

Full

(WxDxH)

(Un-

ted

 

 

Load

packed)

Loading)

338

 

270

895

1119

937

1171

1000

998

92

91138

128x38x78

9100

270

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

320

1055

1319

1110

1388

1200

1176

92

101457

218x38x78

10750

224

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

360

1187

1484

1110

1388

1200

1323

92

114140

218x38x78

10750

224

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

400

1333

1667

1388

1735

1600

1470

92

126822

218x38x78

11650

243

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

450

1500

1875

1388

1735

1600

1654

92

142675

218x38x78

11650

243

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable

1,4,5,7,8,

2,5,7,8,

6

6,8,9,

13

13

Notes:

 

9,11,12

9,11,12

 

11,12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For explanation of notes, see referenced numbers in 10.1 - Notes

* Nominal Input Power Factor 0.92 lagging at full load; 4% Maximum Total Input Harmonic Current Distortion (THD) at full load.

Appendix A - Series 600 UPS Site Planning Data

87

Page 93
Image 93