Table 8

338-1000 kVA Multi-Module Unit, 600 Volt - Standard Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Required

Maximum

 

 

 

 

 

 

 

 

* Rectifier

Inverter

Battery

Battery

%

Maximum

 

 

Floor

 

 

 

AC

AC

Discon-

Current

Efficiency

Heat Dis-

Dimen-

Approx.

Loading

UPS

 

Input

Output

nect

at End of

at

sipation

sions

Weight

Lb./

Rating

Current

Current

Rating

Discharge

Full Load

BTU/hr.

Inches

Lb.

Sq.Ft.

 

 

 

 

 

 

 

 

 

 

Full

 

(Un-

(Distribu-

 

 

 

 

 

 

 

 

 

 

 

ted

kVA

 

kW

Nom

Max

Nom

Max

Amperes

Amperes

 

Load

(WxDxH)

packed)

Loading)

338

 

270

336

420

325

406

1000

993

92

80131

128x38x78

8300

246

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

320

403

504

385

481

1200

1170

92

94970

164x38x78

9900

229

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

360

448

560

385

481

1200

1316

92

106842

164x38x78

9900

229

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

400

504

630

481

601

1600

1463

92

118713

164x38x78

10600

245

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

450

567

709

481

601

1600

1646

92

133552

164x38x78

10600

245

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

 

500

630

788

601

752

2000

1828

92

148391

164x41x78

12300

263

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750HL

 

600

747

934

722

902

1600

1644

92

178070

164x41x78

13925

298

750LL

 

600

747

934

722

902

2000

2194

92

178070

177x44x82

14600

270

1000

 

800

974

1217

962

1203

2500

2169

93

205514

177x44x82

16555

306

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

900

1096

1369

962

1203

2500

2440

93

231203

177x44x82

16555

306

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable

1,4,5,7,8,

2,5,7,8,

6

6,8,9,

13

13

Notes:

 

9,11,12

9,11,12

 

11,12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For explanation of notes, see referenced numbers in 10.1 - Notes

*Nominal Input Power Factor 0.85 lagging at full load; 9% Maximum Total Input Harmonic Current Distortion (THD) at full load. HL - 750 kVA module with 240 battery cells

LL - 750 kVA module with 180 battery cells

 

 

Table 9

338-1000 kVA Multi-Module Unit, 600 Volt - Standard Module With Optional Low

 

 

 

 

Distortion Input Filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Required

Maximum

 

 

 

 

 

 

 

 

* Rectifier

Inverter

Battery

Battery

%

Maximum

Dimen-

Approx.

Floor

UPS

 

AC

AC

Discon-

Current

Efficiency

Heat Dis-

Loading

 

Input

Output

nect

at End of

at

sipation

sions

Weight

Lb./

Rating

Current

Current

Rating

Discharge

Full Load

BTU/hr.

Inches

Lb.

Sq.Ft.

 

 

 

 

 

 

 

 

 

 

Full

 

(Un-

(Distribu-

kVA

 

kW

Nom

Max

Nom

Max

Amperes

Amperes

 

(WxDxH)

ted

 

 

Load

packed)

Loading)

338

 

270

307

384

325

406

1000

993

92

80131

128x38x78

8700

258

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

320

360

450

385

481

1200

1170

92

94970

164x38x78

10300

238

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

360

405

506

385

481

1200

1316

92

106842

164x38x78

10300

238

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

400

460

575

481

601

1600

1463

92

118713

164x38x78

11150

258

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

450

517

647

481

601

1600

1646

92

133552

164x38x78

11150

258

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

 

500

575

718

601

752

2000

1828

92

148391

164x41x78

12950

277

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750HL

 

600

682

853

722

902

1600

1644

92

178070

164x41x78

14200

304

750LL

 

600

682

853

722

902

2000

2194

92

178070

177x44x82

15450

286

1000

 

800

890

1113

962

1203

2500

2169

93

205514

177x44x82

17400

322

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

900

1012

1265

962

1203

2500

2440

93

231203

177x44x82

17400

322

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable

1,4,5,7,8,

2,5,7,8,

6

6,8,9,

13

13

Notes:

 

9,11,12

9,11,12

 

11,12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For explanation of notes, see referenced numbers in 10.1 - Notes

*Nominal Input Power Factor 0.92 lagging at full load; 4% Maximum Total Input Harmonic Current Distortion (THD) at full load. HL - 750 kVA module with 240 battery cells

LL - 750 kVA module with 180 battery cells

88 Appendix A - Series 600 UPS Site Planning Data

Page 94
Image 94
Liebert Series 600 manual KVA Multi-Module Unit, 600 Volt Standard Module