to clearances required for plumbing, electrical, and control entrances. The clearance dimensions shown in this manual are for reference only and are the minimum required for maintenance of the humidifier. Local and National Codes should be consulted prior to final location and installation of the humidifier. Liebert can not accept responsibility for installation code violations.
1. | Location of the humidifier should be below and |
| as close as possible to the steam distributor |
| location as possible. |
2. | For front and side clearance requirements (for |
| access during installation, maintenance and |
| troubleshooting), see Figure #2. |
3. | If possible, DO NOT locate humidifier any |
| further than absolutely necessary from steam |
| distributor location, as net output will be |
| reduced as a result of heat loss through steam |
| hose. Also, increased static pressure may |
| cause operational problems and necessitate |
| use of the fill cup extension kit and other |
| components. |
4. | Where possible, mount humidifier at a height |
| convenient for servicing. |
In addition, install a minimum of 2 field supplied fasteners in the holes provided in the back of the unit to prevent the unit from being bumped off the wall bracket.
6.Make sure humidifier is level.
7.DO NOT mount humidifier on hot surfaces.
8.If humidifiers are mounted on roof, a thermostatically ventilated weatherproof cabinet by others should be used. Consult factory.
9.DO NOT mount humidifiers in an area where freezing may occur.
10.DO NOT mount humidifiers on vibrating surface.
BLOWER PACKS
1.Blower packs are an optional accessory used to directly distribute steam to localized areas (such as computer rooms) or in structures that do not have a
Figure #4
Built On Blower Pack
5. Wall mounting bracket provided should be |
securely attached horizontally and open edge |
upwards, using |
a minimum of 3 - #12 x 3" long wood screws, |
or better, into a vertical structural surface. If |
any spacer material is used between the |
bracket and the structural material such as |
drywall, increase fastener length accordingly. |
Figure #3
Wall Bracket Mounting Detail
Optional
Blower Pack
Single
Circuit
Humidifier
Supply Air
Grille
WALL |
|
| 7.7” |
FASTENWALL BRACKET | A |
(19.6 cm) | |
(FACTORYSUPPLIED)TO |
|
WALL USING ANCHOR BOLTS |
|
(3) SUPPLIEDBY OTHERS |
|
A 7.7"(19.6cm) 7.7"(19.6cm)
Power And
Control
Wiring
See Figure #6 for mounting clearances.
2.Blower packs are available
- 2 -