Lifebreath 99-MD-KIT Clearances and Requirements, Installation, Connecting Appliances to the HRV

Models: 94-EXCHANGER 99-MD-KIT 94-EXCHANGER-MD

1 24
Download 24 pages 25.42 Kb
Page 4
Image 4
Clearances and Requirements

Clearances and Requirements

Connecting Appliances to the HRVWARNING

Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed, by measuring the air flows of the ventilator, by using the balancing procedure found in this manual.

It is always important to assess how the operation of any HRV may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.)

NEVER install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment!!!

Connecting Appliances to the HRV

The following appliances should not be connected to the HRV:

clothes dryer

range top

stovetop fan

central vacuum system

NOTE: Connecting any of these to the HRV will CAUTION

Lint, dust or grease will collect in the HRV damaging the unit.

NOTE: Connecting any of these to the HRV will

invalidate your warranty.

Installation

Installation WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.

Location Selection WARNING

Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.

Location Selection

The HRV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room or an area close to the outside wall where the weather hoods will be mounted. If a basement area is not convenient or does not exist, a utility or laundry room may be used.

Attic installations are not normally recommended due to:

A)the complexity of work to install

B)freezing conditions in the attic

C)difficulty of access for service and cleaning

The HRV unit must be installed in a horizontal position as shown in the illustration below. The unit should be sus- pended using the provided hanging straps. If necessary, the unit may be installed on a platform: however, the cabi- net should be isolated from the platform to prevent vibration transmission. The unit must be level. Sufficient clearance at the front of the access door is required for servicing the air filters and core. A minimum of 25" (635mm) clearance is recommended so the door can be opened. Four PVC reinforced polyester hanging straps are provided for hanging the HRV from the basement floor joists.

Suspending the Unit

The hanging straps should be attached to the unit at the top end corners (mounting screws are already located on the HRV case). Securely fasten the other end of the straps to the floor joists with wide head nails (not supplied), mak- ing sure the UNIT IS LEVEL. The straps are designed to reduce the possibility of noise, resonance or harmonics; therefore using the full length of the strap between the HRV and the floor joists is recommended.

Weather Hood Location and Installation

Weatherhood kit includes two fixed-cover hoods with a 1/4” (6mm) mesh screen.

Exhaust Weather Hood Requirements

At least 6' (2 m) from the ventilation air intake*

At least 18" (457mm) above ground or above the depth of expected snow accumulation*

4

Page 4
Image 4
Lifebreath 99-MD-KIT Clearances and Requirements, Installation, Connecting Appliances to the HRV, Location Selection