CAUTION
Unit must be installed level to ensure proper condensate drainage. Due to the broad range of installation and operational conditions, consideration must be given for the possibility of condensation forming on the unit or
connecting ducting. Objects below the installation may be exposed to condensate.
•At least 3' (1 m) away from the corner of the building*
•At least 3’ away from gas meter, electric meter or a walkway where fog or ice could create a hazard*
•Not into a garage, workshop or other unheated space
When installing the weather hood, its outside perimeter must be sealed with exterior caulking.
* Local code may require greater distances.
Intake Weather Hood Requirements
•Should be located upstream (if there are prevailing winds) from the exhaust outlet
•At least 6' (2 m) from the exhaust weather hood *
•At least 6' (2 m) away from dryer vents and air handler exhaust (medium or high efficiency furnaces)*
•A minimum of at least 6' (2 m) from driveways, oil fill pipes, gas meters, or garbage containers, swimming pools*
•At least 18" (457mm) above the ground, or above the depth of expected snow accumulation*
•At least 3' (1 m) from the inside/outside corner of the building*
•Do not locate in a garage, attic or crawl space
* Local code may require greater distances.
Suspending the Unit using the Provided Hanging Straps
Weatherhood Installation
SCREEN (sidew)
12"anized pipe
EXTERIOR
1/4" | WALL |
| |
| (frontw) |
COLLARTO ENSUREVAPOURARRIER
ISTO WALLTE
Weather Hood Clearances
OUTSIDE CORNER | 36" (1m) | 36" (1m) | INSIDE CORNER | ||||||
|
|
|
|
| recommended min. | recommended min. |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 6' (2m) |
| recommended min. |
INTAKE | EXHAUST |
18" (460mm) min. | 18" (460mm) min. |
1.Thermal sleeve
2.Fasten
3.Slide the fasten
4.Hood for
CAUTION
Weatherhood arrangement - requires a minimum of 6' (2m) separation and a minimum of 18" (460mm) clearance above the higher of the grade or anticipated snow level.