Lifebreath AH80BHW, AH40DHW, AH60DHW Shut Off Valves, Drain Valve, Throttling Valve, Check Valves

Models: AH60BHW AH80BHW AH40BHW AH40DHW AH60DHW

1 32
Download 32 pages 22.01 Kb
Page 8
Image 8
Shut Off Valves

Shut Off Valves

There are 3 shut off valves required for an integrated combo system as follows:

One valve (a) on the cold water side of the water heater upstream of the heating loop con- nection. This valve has the ability to isolate the hot water (domestic and space heating) from the household cold water supply. This valve is required on every waterheater whether or not the water heater is used for space heating.

One valve (b) on the hot water supply side of the heating loop, downstream of its connection to the domestic water.

One valve (c) on the return side of the heating loop upstream of its connection to the domes- tic cold water.

The two valves in the heating loop allow the heating loop to be isolated for service or repair.

(a)(a) Supply Supply

(b)

(c) Return

H C

SHUT OFF VALVES

Drain Valve

system. The drain valve should be near the low point of the return piping system upstream of the shut off valve and is preferred to be near the water heater.

Throttling Valve

The throttling (balancing) valve is used to reduce the water flow rate and thereby increase the water temperature drop. This is done to ensure proper activation of the water heater thermostat. This valve should be a globe or balancing valve.

Check Valves

A spring loaded check valve is required in the heating loop to help minimize thermo-siphoning of hot water throughout the heating loop when heating is not called for and cold water back flowing through the heating loop when domestic hot water is used. The valve will have a water flow direction arrow marked on it’s exterior surface and must be installed with that arrow pointing downstream.

CHECK VALVE

A drain valve is required to allow the heating loop to be drained for service or repair and to remove air from the heating loop when commissioning a

*Check valves should always be installed in a vertical rise with the flow of water shown.

8

Page 8
Image 8
Lifebreath AH80BHW Shut Off Valves, Drain Valve, Throttling Valve, Check Valves, aSupply b c Return H C SHUT OFF VALVES