READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE

This fixture is intended for installation in accordance with the National Electrical Code and local regulations. To assure full compliance with local codes and regulations, check with your local electrical inspector before installation. To prevent electrical shock, turn off electricity at fuse box before proceeding.

Retain these instructions for maintenance reference.

NEW INSTALLATION

A. INSTALLING EMERGENCY BALLAST TO STANDARD FRAME-IN KIT (Fig. 1 and 8).

1.Before placing FRAME-IN KIT in the ceiling, install EMERGENCY BALLAST to the center of MOUNTING FRAME BRACKET as shown.

2.Tighten SCREW to secure two units together.

3.Remove JUNCTION BOX COVER and appropriate J-Box K.O., then attach

EMERGENCY BALLAST BX CONNECTOR.

WIRING - Read and understand all instructions before proceeding.

Make sure AC power is off at the fuse box.

Regular ballast and emergency ballast must be fed from the same branch circuit.

Be sure all electrical connections are made and junction box is closed before connecting inverter connectors in switch/indicator light box.

In switched fixtures, emergency ballast must be connected ahead of any local switching.

Emergency ballast is shipped from the factory ready for 120V or 277V supply connection. Line Voltage selecton is made at switch box. For 120V, remove wire nut from 120V lead (black) and connect to black lead of test switch, then cap the 277V lead (orange).

B.INSTRUCTIONS FOR WIRING EMERGENCY BALLAST FOR (1) OR (2) 4-PIN LAMPS ELECTRONIC A.C. BALLAST FRAME-IN KIT

1.Before converting to emergency lighting, please identify no. of lamps and wattage of frame-in kit, then select appropriate Wiring Diagram A, B or C for rewiring. There is a requirement to remove lamp leads from A.C. ballast, and reconnect to emergency ballast.

2.Disconnect either BLUE LAMP LEAD from BALLAST by inserting conductor of RED JUMPER (provided) into open terminal of QUICK CONNECTOR of BALLAST as shown in Fig. 2. Gently pull BLUE LAMP LEAD out. Then remove RED JUMPER for later use.

3.Repeat step 2 (above) to remove other BLUE LAMP LEAD, and one appropriate RED OR YELLOW LAMP LEAD from BALLAST (Fig. 2) and wiring diagrams.

4.Insert appropriate RED OR YELLOW JUMPER into the terminal where the RED

OR YELLOW LAMP LEAD was previously removed from QUICK CONNECTOR (Fig. 3).

5.Follow WIRING DIAGRAM A, or B, or C to complete the wiring at FLEX “A”.

Fig. 1

 

 

 

 

 

 

 

 

 

 

FRAME-IN KIT

 

 

EMERGENCY

 

 

 

BALLAST

 

 

BX

 

 

 

 

 

 

 

 

 

 

MOUNTING

 

CONNECTOR

 

 

 

FRAME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRACKET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J-BOX

 

SWITCH/

 

 

 

INDICATOR

 

 

COVER

 

BRACKET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SOCKET

 

SCREW

 

 

 

 

CUP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 2

 

BLUE LAMP

INSERT

 

LEADS

RED

 

 

 

 

JUMPER

RED LAMP

 

LEADS

 

 

 

QUICK

 

 

CONNECTOR

Fig. 3

RED INSERT

JUMPER

QUICK

CONNECTOR

WIRING DIAGRAM A (1-LAMP FIXTURE) (1 LAMP EMERGENCY)

NOTE: FOR UNSWITCHED CIRCUIT, CONNECT

 

 

 

 

 

BOTH WHITE/RED AND ORANGE/BLACK LEADS

UNSWITCHED

COMMON

 

 

IN JUNCTION BOX TO UNSWITHCHED 120V

120V OR

 

 

 

277V

(NETURAL)

GROUND

 

OR 277V. VOLTAGE SELECTION IS MADE IN

 

 

 

 

For dimming ballast, connect

SWITCH BOX.

 

 

 

 

 

 

 

dimming leads to dimmer

 

 

 

 

 

WALL

 

WHITE*

GREEN

 

 

 

 

 

 

SWITCH

 

 

 

 

BLK 120V

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

WHT / BLK

 

 

BLACK

 

 

 

 

 

 

TEST

 

 

WHT / RED

 

 

 

 

 

ORG 277V

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

ORG / BLK

 

 

 

 

 

BLACK

ORG/BLK

 

 

 

 

 

 

 

EMERGENCY

 

 

 

 

 

 

 

 

 

 

B

W G

 

 

 

 

 

 

 

 

 

BALLAST

WHITE

 

 

 

 

RED

 

 

 

ELECTRONIC

 

 

 

 

 

 

 

 

 

 

 

FLEX

FLEX

WHT/BLK

 

 

A.C. BALLAST

 

 

 

 

 

 

 

 

 

INVERTER

"B"

"A"

BLUE/WHT

 

 

 

 

 

CONNECTOR

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

RED

 

 

 

Y Y R R

 

BROWN -

 

 

YEL/BLK

 

 

 

 

CHARGE

 

 

YEL

 

 

B

B

LIGHT

 

 

 

 

 

 

 

 

VIOLET +

 

 

 

 

 

 

 

 

 

 

 

 

 

RED*

 

 

 

 

JUNCTION

 

 

 

 

SWITCH BOX

 

 

 

 

RED

 

 

BOX

 

 

 

 

 

 

 

 

 

 

 

 

 

STAB-IN CONNECTOR (2 CONDUCTORS)

 

 

BLUE** BLUE**

RED**

RED

 

 

 

STAB-IN CONNECTOR (3 CONDUCTORS)

 

 

 

 

 

 

 

 

* WHITE AND RED JUMPERS PROVIDED

 

 

 

 

LAMPHOLDER

 

 

 

 

 

 

 

 

** (2) BLUE AND (1) RED LEADS REMOVED

 

 

 

 

 

 

 

FROM ELECTRONIC BALLAST

 

 

 

 

 

 

 

WIRING DIAGRAM B (2-LAMP FIXTURE) UP TO 2-42W

(1 LAMP EMERGENCY)

NOTE: FOR UNSWITCHED CIRCUIT, CONNECT

BOTH WHITE/RED AND ORANGE/BLACK LEADS UNSWITCHED

IN JUNCTION BOX TO UNSWITHCHED 120V

120V OR

COMMON

277V

(NETURAL) GROUND

OR 277V. VOLTAGE SELECTION IS MADE IN

 

 

 

 

For dimming ballast, connect

 

 

 

 

SWITCH BOX.

 

 

 

 

dimming leads to dimmer

 

 

 

 

 

WALL

 

 

 

WHITE*

GREEN

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

BLK 120V

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

WHT / BLK

 

 

BLACK

 

 

 

 

 

 

 

 

TEST

 

 

WHT / RED

 

 

 

 

 

 

ORG 277V

 

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORG / BLK

 

 

 

 

 

 

BLACK

ORG/BLK

 

 

 

 

 

 

 

 

EMERGENCY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

W G

 

 

 

 

 

 

 

 

 

 

 

BALLAST

WHITE

 

 

 

 

 

 

RED

 

 

 

 

 

ELECTRONIC

 

 

 

 

 

 

 

 

 

 

 

 

 

FLEX

FLEX

WHT/BLK

 

 

 

 

A.C. BALLAST

 

 

 

 

 

 

 

 

 

 

 

INVERTER

"B"

"A"

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTOR

 

 

BLUE / WHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

RED

 

 

 

 

B

B Y Y R R

 

 

 

 

 

YEL/BLK

 

 

 

 

 

BROWN -

 

 

 

 

 

 

 

 

CHARGE

 

 

YEL

 

 

 

 

 

 

LIGHT

 

 

 

 

 

 

 

 

 

 

VIOLET +

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

JUNCTION

 

 

 

 

 

 

 

SWITCH BOX

 

 

 

 

 

 

BLUE / WHT

 

 

 

BOX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YELLOW*

 

 

STAB-IN CONNECTOR (2 CONDUCTORS)

 

 

 

 

 

 

 

YELLOW

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

STAB-IN CONNECTOR (3 CONDUCTORS)

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

* WHITE AND YELLOW JUMPERS PROVIDED

 

BLUE**

BLUE**

YEL**

YEL

RED

RED

 

 

FROM ELECTRONIC BALLAST

 

 

 

** (2) BLUE AND (1) RED LEADS REMOVED

 

 

 

 

 

 

 

 

 

LAMPHOLDER 1

 

 

 

 

 

 

 

LAMPHOLDER 2

 

 

(EMERGENCY)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VIOLET

 

 

 

 

 

 

 

 

 

 

TAN

 

 

 

 

®

LIGHTOLIER a GENLYTE THOMAS company.

631 Airport Road, Fall River, MA 02720

Page 2
Image 2
Lightolier IS FAEM3, LIGHTOLIER a GENLYTE THOMAS company, New Installation, C0506, Airport Road, Fall River, MA