Lincoln Electric IM10005 manual Electrical Output Connections, Welding Cable Connections

Models: IM10005

1 46
Download 46 pages 6.32 Kb
Page 11
Image 11

A-4

INSTALLATION

A-4

BULLDOG™ 140 OUTPUT CONNECTIONS

 

 

FIGURE A.1

 

7

1

6

4

 

 

 

5

 

 

3

 

 

 

2

 

1.

CURRENT CONTROL DIAL

5.

RECEPTACLE - 240 VOLT, 50 AMP

2.

WELD OUTPUT TERMINALS (2)

6.

DUPLEX RECEPTACLE (2)- 120 VOLT, 20

3.

GROUND STUD

 

AMP

4.

CIRCUIT BREAKER 20 Amp

7.

HOUR METER

ELECTRICAL OUTPUT

CONNECTIONS

See Figure A.1 for the location of the current control dial, weld output terminals, ground stud, circuit breakers, 240 and 120 volt receptacles.

WELDING CABLE CONNECTIONS

Cable Size and Length

Be sure to use welding cables that are large enough. The correct size and length becomes especially important when you are welding at a distance from the welder.

Table A.1 lists recommended cable sizes and lengths for rated current and duty cycle. Length refers to the distance from the welder to the work and back to the welder. Cable diameters are increased for long cable lengths to reduce voltage drops.

TABLE A.1

RECOMMENDED WELDING CABLE

SIZE AND LENGTH

TOTAL COMBINED LENGTH OF

ELECTRODE AND WORK CABLES

 

Cable

125 Amps

 

 

Length

30% Duty Cycle

 

0-50 ft

(0-15m)

6 AWG

 

 

 

 

 

 

50-100 ft

(15-30 m)

5 AWG

 

 

 

 

 

 

100-150 ft

(30-46 m)

3 AWG

 

 

 

 

 

 

150-200 ft

(46-61 m)

2 AWG

 

 

 

 

 

 

200-250 ft

(61-76m)

1 AWG

 

 

 

 

 

 

 

 

 

 

BULLDOG™ 140

Page 11
Image 11
Lincoln Electric IM10005 manual Electrical Output Connections, Welding Cable Connections