INSTALLATION |
TECHNICAL SPECIFICATIONS – DC-1000
INPUT - THREE PHASE ONLY
Standard
Voltage
230/460/60
575/60
220/380/440/50/60
380/500/50/60
415/50/60
Input Current at Rated Output
100% Duty Cycle | 60% Duty Cycle | 50% Duty Cycle |
193/96.5 | 215/108 | 230/115 |
77.2 | 86 | 92 |
193/112/96.5 | 215/124/108 | 230/133/115 |
112/85 | 124/94 | 133/101 |
102 | 113 | 121 |
|
|
|
RATED OUTPUT
Duty Cycle
100% Duty Cycle
60% Duty Cycle
50% Duty Cycle
Output Range
Amps
1000
1140
1250
OUTPUT
Maximum Open Circuit Voltage
75V for 60 HZ models
72V for 50/60 HZ models
Volts at Rated Amperes
44
44
44
Auxiliary Power
See the OPERATION section
for Auxiliary Power
information by model
RECOMMENDED INPUT WIRE AND FUSE SIZES
INPUT | HERTZ | INPUT AMPERE | TYPE 75°C | TYPE 75°C | TYPE 75°C | |
COPPER WIRE | GROUND WIRE | (SUPER LAG) | ||||
VOLTAGE / |
| RATING ON | ||||
| IN CONDUIT | IN CONDUIT | OR BREAKER | |||
FREQUENCY |
| NAMEPLATE | ||||
| SIZE (AMPS)1 | |||||
|
|
| ||||
|
|
| 30°C (86°F) Ambient |
|
| |
|
|
|
|
|
| |
230 | 60 | 193 | 000 (85) | 4 (21) | 300 Amp | |
460 | 60 | 96.5 | 3 (27) | 6 (14) | 150 Amp | |
575 | 60 | 77.2 | 4 (21) | 6 (14) | 125 Amp | |
220 | 50/60 | 193 | 000 (85) | 4 (21) | 300 Amp | |
380 | 50/60 | 112 | 2 (34) | 6 (14) | 175 Amp | |
415 | 50/60 | 102 | 2 (34) | 6 (14) | 150 Amp | |
440 | 50/60 | 96.5 | 3 (27) | 6 (14) | 150 Amp | |
500 | 50/60 | 85 | 4 (21) | 6 (14) | 125 Amp | |
|
|
|
|
|
|
PHYSICAL DIMENSIONS
HEIGHT | WIDTH | DEPTH | WEIGHT |
30.75 in | 22.25 in | 39.0 in | 821 lbs. |
781 mm | 567 mm | 991 mm | 372 kg. |
|
|
|
|
1Also called “inverse time” or “thermal/magnetic” circuit breakers; circuit breakers which have a delay in tripping action that decreases as the magnitude of the current increases.