Lincoln Electric IM575 manual Troubleshooting & Repair

Models: IM575

1 28
Download 28 pages 18.51 Kb
Page 16
Image 16

8

TROUBLESHOOTING & REPAIR

8

 

 

 

 

Observe all Safety Guidelines detailed throughout this manual

 

PROBLEMS

(SYMPTOMS)

POSSIBLE CAUSES/REMEDIES

3.BLOWER OVER TEMPERATURE a. Airflow restrictions present at load bank intake or exhaust. indicator lights are on, but the

blower is operating.

b. Maximum rating of the load bank may have been exceeded.

4.Fan blade is broken or not turning. a. Fan blade motion may be obstructed.

b.Fan blade may be loose at hub or is not keyed properly.

5.Load step(s) cannot be energized. a. Check to see if over temperature indicator is lit. (See problem 3.)

b.A blower failure may exist. (See problem 2.)

c.Master load switch may be faulty.

d.Control power may be inadequate.

e.Fuse may be blown in load bank control circuit. (Check and replace as required).1.

f.Load step switch may be faulty.

g.Load step contactor may be inoperative.

h.Load step resistor may be open.

i.Output polarity connection is incorrect. Verify correct polarity connection to the load bank.

1.When checking fuses for continuity, be sure to remove all fuses from clips (in fuse block or disconnect switch). Test each fuse individually, out of circuit.

CAUTION

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you proceed. Call 216-383-2531 or 1-800-833-9353.

MASTER LOAD 750

Page 16
Image 16
Lincoln Electric IM575 manual Troubleshooting & Repair