A-5

INSTALLATION

A-5

 

 

 

TABLE A-1

TOTAL COMBINED LENGTH OF ELECTRODE AND WORK CABLES

The 240 VAC output can be split to provide two sepa- rate 120 VAC outputs with a max permissible current of 44 Amps per output to two separate 120 VAC branch circuits (these circuits cannot be paralleled). Output voltage is within ± 10% at all loads up to rated

Cable Length

0-100Ft. (0-30meters)

100-150 Ft. (30-46m meters)

150-200 Ft. (46-61 meters)

Cable Size for

305Amps

100% Duty Cycle

1/ 0 AWG

2 / 0 AWG

3 / 0 AWG

capacity.

The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

CABLE INSTALLATION

Install the welding cables to your RANGER 305D as follows.

1.The diesel engine must be OFF to install welding cables.

2.Remove the flanged nuts from the output terminals

.

3.Connect the electrode holder and work cables to the weld output terminals. The terminals are identified on the case front.

4.Tighten the flanged nuts securely.

5.Be certain that the metal piece you are welding (the “work”) is properly connected to the work clamp and cable.

6.Check and tighten the connections periodically.

CAUTION

Loose connections will cause the output termi- nals to overheat. The terminals may eventually melt.

Do not cross the welding cables at the output ter- minal connection. Keep the cables isolated and separate from one another.

------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

The auxiliary power of the RANGER 305D consists of two 20 Amp-120 VAC (5-20R) duplex receptacles and one 50 Amp 120/240 VAC (14-50R) receptacle. The 240 VAC receptacle can be split for single phase 120 VAC operation.

The auxiliary power capacity is 10,500 watts Peak, 10000 Watts Continuous of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equiva- lent to volt-amperes at unity power factor. The max permissible current of the 240 VAC output is 44 amps.

NOTE: The 240 V receptacle has two 120 V circuits, but are of opposite polarities and cannot be paral- leled.

STANDBY POWER CONNECTIONS

The RANGER 305D is suitable for temporary, stand- by or emergency power using the engine manufactur- er’s recommended maintenance schedule.

The RANGER 305D can be permanently installed as a standby power unit for 240 VAC, 3 wire, single phase, 44 amp service. Connections must be made by a licensed electrician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes.

Install the double-pole, double-throw switch between the power company meter and the premis- es disconnect. Switch rating must be the same or greater than the customer’s premises disconnect and service over current protection.

Take necessary steps to assure load is limited to the capacity of the RANGER 305D by installing a 50 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 44 amperes. Loading above the rated output will reduce output voltage below the allow- able - 10% of rated voltage which may damage appliances or other motor-driven equipment and may result in overheating of the RANGER 305D engine and/or alternator windings.

Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit or as part number T12153-9.)

Plug this cable into the 50 Amp, 120/240 Volt receptacle on the RANGER 305D case front.

RANGER 305D

Page 13
Image 13
Lincoln Electric IM730 manual Total Combined Length of Electrode and Work Cables, Auxiliary Power Receptacles, Table A-1