Lochinvar 1.0- 1.3- 1.5 operation manual Cascade, DHW with remote control, Monitoring Only

Models: 1.0- 1.3- 1.5

1 24
Download 24 pages 39.59 Kb
Page 16
Image 16

Modbus Instructions

5Unit Operation

DHW with remote control:

This installation may or may not have the hot water generator in close proximity to the boiler. Its sensors and thermostat values are only available through the Modbus communication bus.

To ensure that the SYNC boiler can properly respond to a call for hot water generation the following holding registers must be set in addition to other commands:

Holding Registers

Definition

Bit Value (HEX)

Action

 

 

 

 

40001

Configuration

00 4A

Set Configuration to read 40002, 4 & 5

 

 

 

 

40002

Coils

00 08

Enables Tank Tstat (00 00 disables unit)

 

 

 

 

40004

Tank Setpoint

0# ##

Sets Setpoint

 

 

 

 

40005

Tank Temperature

0# ##

Passes tank temp from remote sensor

 

 

 

 

NOTE: To ensure proper operation re-send the configuration bits to holding register 40001 prior to issuing a command.

For proper hexadecimal conversion of rate percentage, please refer to the Rate and Temperature Conversion section on page 17 of this manual.

Cascade

In order to operate the SYNC boiler in Cascade with Modbus communications, configure the leader boiler per the demand configurations in this manual. Connect the remaining boilers in the cascade through the normal cascade communications wiring. Cascade control can then be accomplished automatically through the leader boiler.

Please note that with Modbus communication connected to only the leader boiler, total Cascade information can be seen through the communications link. If you wish to see all the individual temperatures of each unit in the Cascade, each unit will have to have a Modbus communication board. However, each unit can be monitored without the need to control each one individually.

Monitoring Only

Any SYNC boiler can be equipped with the Modbus communication board and then be set up to operate with its own internal controls. If necessary, Modbus can be configured as a monitoring device by selecting demand configurations 1 - 3, and polling the Modbus board for the read only variables.

16