Lochinvar 1.0- 1.3- 1.5 Unit Operation with Modbus Communications, Demand Configuration

Models: 1.0- 1.3- 1.5

1 24
Download 24 pages 39.59 Kb
Page 14
Image 14

Modbus Instructions

5Unit Operation

Unit Operation with Modbus Communications

To control a SYNC boiler through a Building Management System communicating through Modbus, the SYNC Demand Configuration must be set to a value of 4, 5, or 6. These configurations allow different control points for a variety of applications. The configuration can be set by selecting Main>>Setup>>Service/Setup>>Demand Config.

Figure 5-1_Setup Screen

The SYNC boiler is equipped with a Modbus communication timer. This timer is programmable from 0 - 120 seconds. The timer can be programmed from the Modbus Setup Menu by selecting Main>>Setup>>BMS>>Modbus Timeout. The purpose of the timer is to ensure proper temperature data is communicated to the boiler in a timely manner. Additionally, it will provide for fail safe operation should Modbus communication be lost. This timer will cause the unit to revert back to internal unit controls should the Modbus communication be interrupted longer than the Modbus timer. The timer is reset every time a Modbus write command is received with updated temperatures or commands. It is the recommendation of Lochinvar that this timer be set to the shortest value possible.

When controlling a SYNC boiler through a Building Automation System (BAS), it is very important to ensure that the correct configuration bits are sent to holding register 40001, and that the correct data and enable signals are sent to holding registers 40002 - 40007, per the demand configuration.

Demand Configuration 4

In this configuration the unit is controlled by setting the setpoints locally on the boiler and providing an enable signal through Modbus communications.

All sensors and limiting devices should be hardwired to the terminal strip on the back of the unit excluding the thermostat enable and tank thermostat enable signal. These signals will be sent to the unit via Modbus.

The holding registers will need to be set as follows:

Holding Registers

Definition

Bit Value (HEX)

Action

 

 

 

 

40001

Configuration

00 01

Set Configuration to read 40002

 

 

 

 

40002

Coils

00 01

Enables unit (00 00 disables unit)

 

 

 

 

NOTE: To ensure proper operation re-send the configuration bits to holding register 40001 prior to issuing a command.

14

Page 14
Image 14
Lochinvar 1.0- 1.3- 1.5 operation manual Unit Operation with Modbus Communications, Demand Configuration