Lochinvar 150 - 500 General Operation, 1Service, How the water heater operates, Saving parameters

Models: 150 - 500

1 36
Download 36 pages 27.5 Kb
Page 8
Image 8
General Operation

Service Manual

1Service

General Operation

How the water heater operates

The Armor water heater uses an advanced stainless steel heat exchanger and an electronic control module that allows fully condensing operation. The blower pulls in gas and air and pushes flue products out of the water heater through the heat exchanger and flue piping. The control module regulates blower speed to control water heater firing rate. The gas valve senses the amount of air flowing into the water heater and allows only the right amount of gas to flow.

Sequence of operation

Table 1 shows control module normal sequences of operation for water heating operation.

Access modes

User

The user can adjust water heating set point using the UP and DOWN buttons at any time during normal operation. By entering the USER code (0704), the user can also change temperature units, time and date, and night setback settings. In user mode, the following parameters can be viewed but not changed: water heater model number; software version; total operating hours, and total cycles.

Installer

Most parameters are available only to the installer, accessible only by entering the installer access code (5309).

Saving parameters

To save parameters:

Press the ENTER/RESET button.

To keep parameter settings only for a current operating cycle:

Press the MENU/EXIT button 1 time to return to the parameter listings; press again to return to the menu listings.

8

Page 8
Image 8
Lochinvar 150 - 500 General Operation, 1Service, How the water heater operates, Sequence of operation, Saving parameters