3Troubleshooting (continued)

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

While the unit is in Service Mode, the outlet

• Establish a heating load to remove the heat from the

 

temperature has exceeded 185°F.

water heater loop.

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

• Verify that the water heater is piped properly into the

 

 

heating system. Refer to Section 6 - System Piping

 

 

of the Armor Water Heater Installation and Operation

 

 

Manual for the proper piping methods for the Armor

Service Blk

 

water heater.

 

 

• Check 120 VAC to the water heater pump motor on a

 

 

call for heat. If voltage is not present, check the wiring

 

 

back to the main control board. Replace the main

 

 

control board if necessary.

 

 

• If 120 VAC is present on a call for heat and the water

 

 

heater pump is not operating, replace the pump.

 

 

• Verify that the water heater pump is set to the proper

 

 

speed or that the water heater pump is the proper

 

 

size. Reference Section 6 - System Piping of the

 

 

Armor Water Heater Installation and Operation

 

 

Manual for water heater pump specifications.

 

 

 

 

120 VAC input to the main control board has

• Check 120 VAC supply to the transformer.

 

dropped below 80 VAC.

 

Low 24 VAC

 

• Check wiring connections at the low voltage terminal

 

strip.

 

 

• Check the wire size/length to remote devices.

 

 

• Replace the transformer.

Watch Dog Error

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

Write EEProm

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

CRC Parameters

internal fault.

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

No Error Stored

internal fault.

 

 

 

 