Lochinvar 151-200 ARMOR 400 WATER HEATER, Vendor, Pump Recommendation For, PUMP-Rec-01Rev C

Models: 151-200

1 5
Download 5 pages 35.61 Kb
Page 3
Image 3
ARMOR 400 WATER HEATER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PUMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommendation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PUMP-Rec-01 Rev C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PUMP RECOMMENDATION FOR

 

 

 

 

 

 

 

 

 

 

 

ARMOR 400 WATER HEATER

 

 

 

 

 

 

 

 

Pump Specifications

 

 

 

 

 

 

 

 

 

 

 

Part No.

 

HorsePower

 

Flanges

Valute Material

 

Flange Material

 

Vendor

 

Vendor Product Series

 

Orientation

 

PUM3012

 

2/5

 

1-1/2"

 

Bronze

 

Bronze

 

Armstrong

 

E Series

 

Vertical

 

 

 

Installation Specifications

 

 

 

 

 

 

 

 

 

 

 

 

Recommended for

 

 

 

 

 

 

Based on

 

 

 

 

 

 

Pump

Model Numbers

 

 

Minimum GPM

 

Installation Type

 

 

 

 

Armor Wtr Htr, AW(N,L) 400

 

 

39 GPM (400)

 

Single Water Heater piped to Single Storage Tank

PUM3012

Based on

 

 

Based on

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Pipe Diameter

 

Connecting piping

 

 

 

 

 

 

 

 

 

 

2"

 

 

 

Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves

 

 

IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds the pump capacity in flow and/or head see “Pump-Curves-All Pumps” for alternate pumps and pump curves.