Lochinvar 1.5 2Maintenance schedule Service technician, Owner maintenance, Daily, Monthly, months

Models: 1.5 1.3 1

1 16
Download 16 pages 33.86 Kb
Page 5
Image 5
2Maintenance schedule

User’s Information Manual

2Maintenance schedule

Service technician

(see the SYNC Service Manual)

General:

Address reported problems, if any

Inspect interior; clean and vacuum if necessary;

Clean condensate trap and fill with fresh water

•Check for leaks (water, gas, flue, condensate)

Verify flue and air lines in good condition and sealed tight

•Check system water pressure/system piping/expansion tank

 

• Check control settings

 

UP

• Check ignition and flame sense

 

electrodes (sand off any deposits; clean

 

START-

and reposition)

 

 

• Check wiring and connections

 

 

 

 

• Perform start-up

checkout

and

ANNUAL

performance verification per Section 9.

• Flame inspection (stable, uniform)

 

 

• Flame signal (at least 10 microamps at

 

high fire)

 

 

 

• Clean the heat

exchanger

if flue

 

temperature is more than 54°F (30°C)

 

above return water temperature.

 

 

• Test low water flow conditions.

 

If combustion or performance indicate need:

Clean heat exchanger

Remove and clean burner using compressed air only

Clean the blower wheel

Owner maintenance

(see pages 6 - 8 for detailed instructions)

• Check boiler area

Daily

• Check pressure/temperature

 

 

gauge

 

 

 

• Check vent piping

 

• Check air piping

Monthly

• Check air and vent termination

 

screens

 

• Check relief valve

 

• Check condensate drain system

 

• Check automatic air vents

 

 

 

• Test low water cutoff

Every

• Reset button (low water cutoff)

6 months

 

 

• Check boiler piping (gas and

 

water) for leaks

 

• Operate relief valve

 

 

End

•Shut boiler down (unless boiler

of season

used for domestic hot water)

months

 

￿WARNING

Follow the maintenance procedures given throughout this manual. Failure to perform the service and maintenance or follow the directions in this manual could result in damage to the boiler or system, resulting in severe personal injury, death, or substantial property damage.

5

Page 5
Image 5
Lochinvar 1.5, 1.3 2Maintenance schedule Service technician, Owner maintenance, If combustion or performance indicate need