Installation & Operation Manual

6Hydronic piping

Near boiler piping components

1.

Boiler system piping:

 

Boiler system piping MUST be sized per the pipe

 

requirements listed in Table 6A. Reducing the pipe size

 

can restrict the flow rate through the boiler, causing

 

inadvertent high limit shutdowns and poor system

 

performance. Flow rates are based on 20 feet of piping,

 

4 - 90° elbows, and 2 - fully ported ball valves.

2.

Boiler circulating pump:

 

A Grundfos UPS26-99F pump will be provided by the

 

factory (for standard altitude models) as the boiler

 

circulation pump based on 20 feet of piping, 4 - 90°

 

elbows, and 2 - fully ported ball valves.

 

Knight wall mount boilers are capable of controlling a

 

variable speed boiler circulator. Variable speed

 

circulators MUST be sized to meet the specified

 

minimum flow requirements listed in FIG. 6-2 on page 36

 

at full speed.

 

3. Domestic hot water circulating pump:

 

Field supplied. The pump MUST be sized to meet

 

the specified minimum flow requirements listed in

 

FIG. 6-2. Consult the indirect water heater operating

 

guide to determine flow characteristics for the selected

 

product used.

 

4.

Boiler isolation valves:

 

Field supplied. Full port ball valves are required. Failure

 

to use full port ball valves could result in a restricted flow

 

rate through the boiler.

 

5.

Check valves:

 

 

Field supplied. Check valves are recommended for

 

installation as shown in FIG.’s 6-3 through 6-10. Failure

 

to install check valves could result in a reverse flow

 

condition during pump(s) off cycle.

6. Domestic indirect hot water isolation valves:

 

Field supplied.

Full port ball valves are

11.Boiler purge valve:

Field supplied. The boiler purge valve is used to remove entrapped air from the heat exchanger during start-up.

12.System temperature sensor:

Lochinvar supplies a system temperature sensor. The sensor is to be installed in the heating loop downstream from the boiler hot water piping and heating loop junction. Typically the sensor will be located far enough downstream to sense system diluted water temperature.

13.Indirect water heaters:

The Knight wall mount boiler may be piped to an indirect water heater to heat domestic hot water with the space heat transfer medium. As depicted in the piping diagrams on page 38 thru 45, there are two options when utilizing an indirect water heater.

A.The space heating piping will branch off to flow the space heat transfer medium through a single wall heat exchanger coil inside the indirect water heater.

B.The indirect water heater is connected to the system supply piping. A pump controlled by the Knight (wall mount) boiler’s control will regulate the flow of water through the indirect water heater. The indirect water heater’s temperature will be regulated by the Knight (wall mount) boiler’s control.

The Knight wall mount boiler is pre-configured to control the operation of the DHW pump with Domestic Hot Water Prioritization programming. The DHW programming is designed to control and balance the space heating demand by switching between DHW and space heating.

Lochinvar offers the Squire which is a series of indirect water heaters. The Squire features a stainless steel vessel with a single wall stainless steel heat exchanger.

 

required. Failure to use full port ball valves could

 

result in a restricted flow rate through the boiler.

7.

Anti-scald mixing valve:

 

Field supplied.

An anti-scald mixing valve is

 

recommended when storing domestic hot water above

 

115°F.

 

8.

Unions:

 

 

Field supplied. Recommended for unit serviceability.

9.

Temperature and pressure gauge:

 

Factory supplied. The temperature and pressure gauge is

￿WARNING

The National Standard Plumbing Code, the National Plumbing Code of Canada and the Uniform Plumbing Code limit the pressure of the heat transfer fluid to less than the minimum working pressure of the potable water system up to 30 psi maximum. Also, the heat transfer fluid must be water or other non-toxic fluid having a toxicity of Class 1, as listed in Clinical Toxicology of Commercial Products, 5th Edition.

shipped loose. It is the responsibility of the contractor to

install the temperature and pressure gauge on the boiler

water outlet.

10. Pressure relief valve:

Factory supplied. The pressure relief valve is sized to

ASME specifications.

34

14.Y-Strainer:

Field supplied. A Y-strainer or equivalent multipurpose strainer is recommended at the inlet of the heat exchanger to remove system particles from older hydronic systems and protect newer systems.

Page 34
Image 34
Lochinvar 51 operation manual Near boiler piping components

51 specifications

Lochinvar 51 is an innovative and robust residential boiler system designed for high-efficiency heating needs. A popular choice among homeowners, the Lochinvar 51 stands out in the market due to its advanced features and eco-friendly technologies.

One of the main features of Lochinvar 51 is its compact design, making it ideal for installation in limited space environments such as attics or closets. Despite its small footprint, it boasts a powerful heating capacity, suitable for varying home sizes. The boiler operates with a modulating gas burner that allows it to adjust its heat output according to the demand, ensuring efficiency and comfort throughout the day.

The Lochinvar 51 employs a cutting-edge heat exchanger made from stainless steel, which is highly durable and resistant to corrosion. This design not only enhances the boiler's performance but also increases its lifespan. The unit offers impressive AFUE (Annual Fuel Utilization Efficiency) ratings, showcasing its capability to convert a significant portion of fuel into usable heat, thus minimizing energy waste and reducing heating costs.

Technologically, the Lochinvar 51 is equipped with advanced control systems that facilitate precise temperature management. The intuitive interface allows homeowners to easily set their desired temperature and monitor the system’s performance. Additionally, the integration of outdoor reset technology helps optimize energy consumption by adjusting the water temperature based on outside weather conditions, leading to further energy savings.

Safety features are also paramount in the Lochinvar 51. It includes built-in safeguards that monitor pressure and temperature, automatically shutting down the system in case of any irregularities. This not only protects the boiler but also ensures peace of mind for users.

Moreover, Lochinvar 51 supports compatibility with smart home systems, providing homeowners with remote control capabilities via mobile devices. This innovative feature enhances user convenience, allowing for easy adjustments and monitoring of the heating system from anywhere.

In conclusion, the Lochinvar 51 is an exceptional choice for homeowners looking for a reliable, efficient, and technologically advanced heating solution. With its impressive heating capacity, durable design, and innovative control features, it sets a high standard in residential boiler performance, making it a top contender in today’s market.